Specifications
201 Rev. 3
WIRING DIAGRAMS
TO AVOID POSSIBLE ELECTRICAL SHOCK, PERSONAL INJURY
,
OR DEATH, DISCONNECT THE POWER BEFORE SERVICING.
WARNING
VCB18-60A2A, RCA/B18-60A2A/B & RCB30A2C
NOTES
1. SEE ELECTRICAL INFORMATION ON UNIT NAMEPLATE. FIELD CONNECTIONS FOR
1• UNITS ARE TO BE MADE AT L1, L2 & EQUIPMENT GROUND SCREW.O
2. FOR FIELD CONNECTIONS SEE INSTALLATION INSTRUCTIONS.
3. TRANSFORMER N.E.C. CLASS 2, 24VAC OUTPUT, 20VA MINIMUM.
CANADIAN REQUIREMENTS:
4. NEUTRAL, IF INPUT POWER DERIVED FROM 240/416 SOURCE.
5. CONTROL CIRCUIT GROUND.
6. 120/240 VAC 3 WIRE/FILS.
1. AMANA APPROVED REPLACEMENT PARTS MUST BE USED WHEN SERVICING.
2. TOTAL SYSTEM CHARGE IS MARKED ON CONDENSER NAMEPLATE
WHICH INCLUDES INDOOR SECTION AND 25 FEET OF INTERCONNECTING
.250 LIQUID LINE .20 OZ. PER FOOT
.375 LIQUID LINE .60 OZ. PER FOOT
.500 LIQUID LINE 1.30 OZ. PER FOOT
TOTAL CHARGE BLOCK MUST BE STAMPED BY THE DEALER WHO INSTALLS THE UNIT.
FOR MORE COMPLETE INSTRUCTIONS SEE INSTALLATION INSTRUCTIONS.
FACTORY SUPPLIED WIRING
LOW VOLTAGE
HIGH VOLTAGE
FIELD SUPPLIED WIRING
LOW VOLTAGE
HIGH VOLTAGE
COLOR CODE
1ST GROUP-COLOR
2ND GROUP-NUMBER
OR-ORANGE
YL-YELLOW
VT-VIOLET
BR-BROWN
GN-GREEN
BK-BLACK
BU-BLUE
RD-RED
TN-TAN
10841001 REV 0
LIQUID LINE, IF DIFFERENT LIQUID LINE LENGTH IS USED ADJUST PER
FOLLOWING CHART.
NOTE: READ THE FOLLOWING NOTES BEFORE OPERATING OR SERVICING THIS UNIT.
ACCESSORIES:
WARNING:
WIRING TO UNIT MUST
BE PROPERLY POLARIZED
(AS APPLICABLE) AND
GROUNDED. DISCONNECT
POWER BEFORE SERVICING.
C
S
R
FAN
HERM
COM
CAPACITOR
OUTDOOR
FAN
MOTOR
VT20
BK27
BR11
L2 L1
T1T2
CONTACTOR
(CC)
FIELD CONNECTIONS
1í POWER
SEE NOTES 1&6
GND
BK1
WARNING:
WIRING TO UNIT MUST BE PROPERLY
POLARIZED (AS APPLICABLE) AND GROUNDED.
DISCONNECT POWER BEFORE SERVICING.
SEE
NOTE 5
RD10
BK1
RD10
YL1
Y
CC
C/X
T2
L2L1
GND
R
S
C
OD
COMP
CAP
F
H
C
T1
CC
FAN
YL1
VT20
BK
27
YL
12
BR
11
RD
10
GY-GRAY
COMPRESSOR
VT
20
VT
20
YL12
BK15
INTERNAL
CRANKCASE
HEATER
BK14
BK
15
BK
14