Specifications

CONDENSING UNIT SPECIFICATIONS
14 Rev. 3
IMPORTANT NOTE:
WHILE THIS DATA IS PRESENTED AS A GUIDE, IT IS IMPORTANT TO ELECTRICALLY CONNECT THE UNIT
AND PROPERLY SIZE WIRES AND FUSES/CIRCUIT BREAKERS IN ACCORDANCE WITH THE NATIONAL
ELECTRICAL CODE AND/OR LOCAL CODES.
MODEL
VCA60
B2A
VCA60
B3A
VCB18
A2A
VCB24
A2A
VCB30
A2A
VCB36
A2A
VCB48
A2A
VCB60
A2A
COOLING CAPACITY, BTUH 60000 60000 18000 24000 30000 36000 48000 60000
COMPRESSOR
R.L. AMPS 27.7 18.6 7.2 10.9 12.3 15.3 20.3 26.9
L.R. AMPS 123.0 128.0 49.0 61.0 76.0 86.0 107.4 141.0
CONDENSER FAN MOTOR
HORSEPOWER 1/4 1/4 1/10 1/10 1/10 1/10 1/5 1/5
R.L. AMPS 1.7 1.7 0.6 0.6 0.6 0.6 1.2 1.2
L.R. AMPS 3.7 3.7 1.0 1.0 1.0 1.0 2.3 2.3
LIQUID LINE, INCHES O.D. 3/8 3/8 1/4 1/4 3/8 3/8 3/8 3/8
SUCTION LINE, INCHES O.D
1-1/8 1-1/8 5/8 5/8 3/4 3/4 7/8 1 1/8
REFRIGERANT CHARGE 119.0 oz. 123.0 oz. 54.0 oz. 64.0 oz. 70.0 oz. 85.0 oz. 123.0 oz. 135.0 oz.
POWER SUPPLY
208/230-60-1 208/230-60-3 208/230-60-1 208/230-60-1 208/230-60-1 208/230-60-1 208/230-60-1 208/230-60-1
MIN.CIRCUIT AMPACITY 36.3 25.0 9.6 14.2 16.0 19.8 26.6 35.3
MAX. OVERCURRENT
DEVICE
60 40 15 25 25 35 45 60
ELECT. CONDUIT SIZE
POWER SUPPLY 1/2" or 3/4" 1/2" or 3/4" 1/2 or 3/4 1/2" or 3/4" 1/2 or 3/4 1/2 or 3/4 1/2 or 3/4 1/2 or 3/4
LOW VOLTAGE 1/2" 1/2" 1/2 1/2" 1/2 1/2 1/2 1/2
APPROX. SHIPPING WT 205 205 133 137 145 174 239 259