Installation Instruction
5
Electrical Requirements - U.S.A. Only
If codes permit and a separate ground wire is used, it is 
recommended that a qualified electrical installer determine that 
the ground path and wire gauge are in accordance with local 
codes.
Do not use an extension cord.
Be sure that the electrical connection and wire size are adequate 
and in conformance with the National Electrical Code, ANSI/ 
NFPA 70-latest edition and all local codes and ordinances.
A copy of the above code standards can be obtained from:
National Fire Protection Association
1 Batterymarch Park
Quincy, MA 02169-7471
WARNING: Improper connection of the equipment-grounding 
conductor can result in a risk of electric shock. Check with a 
qualified electrician or service technician if you are in doubt as to 
whether the appliance is properly grounded. Do not modify the 
power supply cord plug. If it will not fit the outlet, have a proper 
outlet installed by a qualified electrician.
Electrical Connection
To properly install your range, you must determine the type of 
electrical connection you will be using and follow the instructions 
provided for it here.
 ■ Range must be connected to the proper electrical voltage 
and frequency as specified on the model/serial rating plate. 
The model/serial rating plate is located on the frame behind 
a top corner of the door or either side of the drawer. Refer 
to the figures in “Product Dimensions” in the “Location 
Requirements” section.
 ■ This range is manufactured with the neutral terminal 
connected to the cabinet. Use a 3-wire, UL listed, 40- or 
50-amp power supply cord (pigtail) (see the following Range 
Rating chart). If local codes do not permit ground through 
the neutral, use a 4-wire power supply cord rated at 
250 V, 40 or 50 amps and investigated for use with ranges.
Range Rating* Specified Rating 
of Power Supply 
Cord Kit and Circuit 
Protection
120/240 Volts 120/208 Volts Amps
8.8 - 16.5 KW 7.8 - 12.5 KW 40 or 50**
16.6 - 22.5 KW 12.6 - 18.5 KW 50
 * The NEC calculated load is less than the total connected load 
listed on the model/serial rating plate.
 ** If connecting to a 50-amp circuit, use a 50-amp rated cord 
with kit. For 50-amp rated cord kits, use kits that specify use 
with a nominal 1³⁄
8
" (34.9 mm) diameter connection opening.
 ■ A circuit breaker is recommended.
 ■ The range can be connected directly to the circuit breaker 
box (or fused disconnect) through flexible or nonmetallic 
sheathed, copper or aluminum cable. See the “Electrical 
Connection - U.S.A. Only” section.
 ■ Allow 2 to 3 ft (61.0 cm to 91.4 cm) of slack in the line so that 
the range can be moved if servicing is ever necessary.
 ■ A UL listed conduit connector must be provided at each end 
of the power supply cable (at the range and at the junction 
box).
 ■ Wire sizes and connections must conform with the rating of 
the range.
 ■ The wiring diagram is located on the Tech Sheet.
 ■ The Tech Sheet is located on the back of the range inside a 
clear plastic bag.
If connecting to a 4-wire system:
This range is manufactured with the ground connected to the 
neutral by a link. The ground must be revised so the green 
ground wire of the 4-wire power supply cord is connected to the 
cabinet. See the “Electrical Connection - U.S.A. Only” section.
Grounding through the neutral conductor is prohibited for new 
branch-circuit installations (1996 NEC); mobile homes; and 
recreational vehicles, or an area where local codes prohibit 
grounding through the neutral conductor.
When a 4-wire receptacle of NEMA Type 14-50R is used, a 
matching UL listed, 4-wire, 250-volt, 40- or 50-amp, range 
power supply cord (pigtail) must be used. This cord contains 
4 copper conductors with ring terminals or open-end spade 
terminals with upturned ends, terminating in a NEMA Type 14-
50P plug on the supply end.
The fourth (grounding) conductor must be identified by a green 
or green/yellow cover and the neutral conductor by a white 
cover. Cord should be Type SRD or SRDT with a UL listed strain 
relief and be at least 4 ft (1.22 m) long.
4-wire receptacle (14-50R)
The minimum conductor sized for the copper 4-wire power cord 
are:
40-amp circuit
2 No.-8 conductors
1 No.-10 white neutral
1 No.-8 green grounding
If connecting to a 3-wire system:
Local codes may permit the use of a UL listed, 3-wire, 
250 V, 40- or 50-amp range power supply cord (pigtail). This 
cord contains 3 copper conductors with ring terminals or 
open-end spade terminals with upturned ends, terminating in a 
NEMA Type 10-50P plug on the supply end. Connectors on the 
appliance end must be provided at the point the power supply 
cord enters the appliance. This uses a 3-wire receptacle of 
NEMA Type 10-50R.
3-wire receptacle (10-50R)










