8. OPERATION INSTRUCTIONS
1.1. Startup Procedure
a. Turn ON the INPUT breaker.
b. Wait 5 seconds for the “Charger LED” to start flashing.
c. Turn ON the BATTERY breaker.
d. Turn ON the OUTPUT breaker.
1.2. Shutdown Procedure
a. Turn OFF the OUTPUT breaker.
b. Turn OFF the BATTERY breaker.
c. Turn OFF the INPUT breaker.
CAUTION: Batteries will become damaged upon
over-discharge. Upon “BATTERY STOP ALARM”,
shutdown loads and the DC UPS System.