Chapter 3 - Operation and Administration of the Macro BTS NPU Configuration
4Motion 439 System Manual
3.4.16.4.2 Disabling Dry-contact Input Alarms
To disable (block) a dry contact input alarm mapped to a specific alarm condition,
run the following command:
npu(config)# no dry-contact IN <alarm_num (1-8)>
alarm
{CommercialPower
Failure | Fire |
EnclosueDoorOpe
n |
HighTemperature |
Flood | LowFuel |
LowBatteryThresh
old |
GeneratorFailure |
IntrusionDetection
|
ExternalEquipment
Failure
Indicates the alarm
condition to be
mapped to a pin
number.
Mandatory N/A
CommercialPowerFai
lure
Fire
EnclosueDoorOpen
HighTemperature
Flood
LowFuel
LowBatteryThreshold
GeneratorFailure
IntrusionDetection
External
ExternalEquipmentFa
ilure (can be used
for defining a
condition other than
the ones specified
by the other
parameters in this
command)
[alarmPolarity
{RaiseOnClose |
RaiseOnOpen }]
Indicates whether
alarm will be raised on
closed or open circuit
condition.
Optional RaiseOn
Close
RaiseOnClose
RaiseOnOpen
Command
Modes
Global configuration mode
NOTE
For more information about mapping dry contact alarms to an alarm condition, refer to
“Mapping
a Dry-contact Input Alarm to an Alarm Condition” on page 436
. For more information
about displaying the alarm condition currently mapped to an alarm, refer to
“Displaying
Configuration Information for Dry-contact Input/Output Alarms” on page 443
.