User Manual
Chapter 3 - Operation and Administration of the Macro BTS NPU Configuration
4Motion 438 System Manual
NOTE
For more information about displaying the alarm conditions currently mapped to the micro D-Type
ALRM-IN/OUT connector pins, refer
Section 3.4.16.6.
Command
Syntax
npu(config)# dry-contact IN <alarm_num (1-8)> alarm {CommercialPowerFailure | Fire |
EnclosueDoorOpen | HighTemperature | Flood | LowFuel | LowBatteryThreshold | GeneratorFailure
| IntrusionDetection | ExternalEquipmentFailure} [alarmPolarity {RaiseOnClose | RaiseOnOpen }]
Privilege
Level
10
Syntax
Description
Parameter Description Presence Default
Value
Possible Values
<alarm_num
(1-8)>
Indicates the alarm
number of the dry
contact input alarm
that is to be mapped
to an alarm condition.
This alarm number
corresponds to a pin
on the 25-pin micro
D-Type jack.
For more information
about the pin numbers
that correspond to the
alarm number, refer
Table 3-26.
Mandatory N/A 1-8