The operator can control the faulty remote unit by pressing the CONTROL button on the left side of the
alarm row. A window will open.
1. Choose the required Command
Remote unit RF Output Enable – On/Off
Counters ResetReset all unlock counters (Pilot/Synthesizers)
Remote unit Reset Reset the remote unit software
Instance 1Turn instance 1 output RF off
Instance 2Turn instance 2 output RF off
2. Press the SEND button
3. Go to specific remote unit information screen or check the Operational remote units status to
verify current status.
Note: Only a single command can be issued!
13.8 Alarms Thresholds
Each remote unit periodically transmits its current status to the monitoring system. An alarm is
generated in a case where one of the remote unit status parameters exceeds a threshold defined in the
system. The operator can configure the alarm thresholds to fit the local requirements.
The following parameters can be configured from the Alarm Thresholds screen:
Minimum Gain Generates an alarm when the remote unit gain is lower than the threshold
Maximum Gain Generates an alarm when the remote unit gain is higher than the threshold
Multiple Units Failure (Quantity>) Generates a multiple units alarm whenever the number of failed
units exceeds the threshold