Installation Guide

- 2 - WayPoint5CEV
WARNING: When installing in a non-restricted service area, use lock or other fastened means on door
latches. This installation should be made by qualified service personnel and should conform to the National
Electrical Code and all local codes.
LED Diagnostics:
Red (DC) Green (AC) Power Supply Status
ON ON Normal operating condition.
ON OFF Loss of AC. Stand-by battery supplying power.
OFF ON No DC output. Short circuit or thermal overload condition.
OFF OFF No DC output. Loss of AC. Discharged or no battery present.
Terminal Identification:
Terminal Legend Function/Description
AC/AC Low voltage input.
+ DC -- 6VDC,12VDCor24VDC@4ampcontinuoussupplycurrent.
+BAT-- Stand-by battery connections. Maximum charge rate 300mA.
Fig. 1
XFMR
6V
CLSD
OPEN
12V
OPEN
OPEN
24V
OPEN
CLSD
SW1
SW2
+ DC --- + BAT --- AC AC
AC
DC
MADE IN U.S.A.
SW1
SW2
SW1
SW2
2A
250V
L
N
Green
Ground
Red Lead
Black Lead
220VAC
50Hz/60Hz
input
Removable
Fuse
2A/250V
WARNING:
HOT SURFACE
DO NOT TOUCH
Fig. 1a
Fig. 1b