Installation Guide

WayPoint30A - 3 -
12. Set illuminated master power disconnect circuit breaker to the [OFF] position (Figs. 2-4, pgs. 4-6).
13. Connecting devices to WayPoint30ADU:
For 24VAC output connect devices to terminals marked [COM, 24V] (Fig. 2, pg. 4).
For 28VAC output connect devices to terminals marked [COM, 28V] (Fig. 2, pg. 4).
Connecting devices to WayPoint30A4U or WayPoint30A4DU:
Connect device to terminals marked [1-4] and [COM] (Fig. 3, pg. 5).
Connecting devices to WayPoint30A8U or WayPoint30A8DU:
Connect device to terminals marked [1-8] and [COM] (Fig. 4, pg. 6).
14. Set illuminated master power disconnect circuit breaker to the [RESET/ON] position (Figs. 2-4, pgs. 4-6).
15. LEDs will illuminate indicating each output is powered (Figs. 2-4, pgs. 4-6).
16. Upon completion of wiring secure enclosure door with latches and optional lock.
Caution: Equipment to be installed / serviced by authorized / trained personnel only.
Shut branch circuit power before installing / servicing equipment.
WARNING: When installing in a non-restricted service area use lock or other fastened means on door
latches. This installation should be made by qualified service personnel and should conform to all local
codes and in accordance with the National Electrical Code.
LED Identification Chart:
ON OFF
Normal operating condition.
No AC output. Blown fuse or tripped PTC, illuminated master power
disconnect circuit breaker is tripped or OFF, AC failure.
To reset a tripped PTC turn the power off for 1 minute and then turn it back on.
Technical Specifications:
Parameter Description
Input power
requirements
115VAC 60Hz, 3 amp or 230VAC 50Hz, 1.5 amp.
Indicators
Individual power output LED indicators.
Illuminated master power switch.
Environmental
Conditions
Operating Ambient Temperature:
For 24VAC @ 12.5 amp output -40°C to 60°C (-40°F to 140ºF).
For 28VAC @ 10.0 amp output -40°C to 70°C (-40°F to 158ºF).
Relative Humidity: 85%, +/- 5%
Storage Temperature: -40ºC to 75ºC (-40ºF to 167ºF).
Operating Altitude: -1000 to 6,561.679 ft. (-304.8 to 2000m).
Regulatory
Compliance
UL Listed for Information Technology Equipment (UL 60950-1) and
Equipment to be Installed Outdoors (UL 60950-22).
CE European Conformity.
For fuse protected models:
Replace blade type fuses with ratings from 3A up to 10A.
WayPoint30A4U and WayPoint30A8U incorporate 5A fuses.
The lightning flash with arrow head symbol within an equilateral triangle is intended to alert the user to the
presence of an insulated DANGEROUS VOLTAGE within the product’s enclosure that may be of sufficient
magnitude to constitute an electric shock.
The exclamation point within an equilateral triangle is intended to alert the user to the presence of important
operating and maintenance (servicing) instructions in the literature accompanying the appliance.
CAUTION: To reduce the risk of electric shock do not open enclosure. There are
no user serviceable parts inside. Refer servicing to qualified service personnel.