Spec Sheet

Tango8AP & Tango8APCB
PoE Driven Multi-output Power Supply/Chargers
Ethernet Input
802.3bt PoE up to 90W or 802.3at up to 30W or 802.3af up to 15W
Power Output (when using 802.3bt 90W)
12VDC up to 5.4A (65W) and/or 24VDC up to 2.7A (65W).
Combined output not to exceed 65W.
When charging batteries:
12VDC up to 4.6A (55W) and/or 24VDC up to 2.3A (55W).
Combined output not to exceed 55W.
Ethernet Output
Pass-through Ethernet Port (data only).
Battery Charging Circuit
12VDC battery charger for Lithium Iron Phosphate Battery (LiFeP0
4
only).
Unique technology allows for single battery to backup.
12VDC and/or 24VDC systems.
Supervision
Loss of PoE Input.
Battery Supervision
Indicators (LED)
Input Indicates input voltage is present.
Output Indicates normal operating condition.
PoE Type PoE Class Indicator
Supervision PoE Fail or BAT Fail.
PDS8/PDS8CB Power Distribution Module:
Inputs:
12VDC and 24VDC from Tango1B, factory wired.
Main Fuse Rating 10A/32V.
Outputs
Tango8AP: Fuse protected outputs rated @ 3A per output,
non power-limited. Total output 20A max.
Tango8APCB: PTC protected outputs rated @ 2A per output,
Class 2 power-limited. Total output 16A max.
Do not exceed the individual power supply ratings.
Any of the eight (8) power outputs are selectable for 12VDC or 24VDC.
Individual outputs may be set to OFF position for servicing.
Indicators (LED)
DC Output Individual voltage LEDs indicate
12VDC (Green) or 24VDC (Green and Red).
ACMS8/ACMS8CB Access Power Controller:
Inputs
12VDC and 24VDC from Tango1B, factory wired.
Current Consumption: 0.6A @ 12V, 0.3A @ 24V with all relays energized
Main Fuse Rating 15/32A.
ACMS8/ACMS8CB Access Power Controller (cont’d):
Trigger Inputs
Eight (8) individually controlled trigger inputs:
a) Normally open (NO) inputs.
b) Normally closed (NC) inputs.
c) Open collector sink inputs.
d) Wet Input (5VDC - 24VDC) with 10K resistor.
e) Any combination of the above.
Outputs
Tango8AP: Eight (8) Fuse protected outputs rated @ 2.5A per output,
non power-limited. Total output 20A max.
Tango8APCB: Eight (8) PTC protected outputs rated @ 2A per output,
Class 2 power-limited. Total output 16A max.
Do not exceed the individual power supply ratings.
Eight (8) selectable 12VDC or 24VDC independently controlled
outputs or eight (8) indepently controlled Form “C” relay outputs:
a) Fail-Safe and/or Fail-Secure power outputs.
b) Form “C” Relays. 28VAC or VDC @ 2.5A Rated.
c) Auxiliary power outputs (unswitched).
d) Any combination of the above.
Any of the eight (8) power outputs are selectable for 12VDC or 24VDC.
Individual outputs may be set to OFF position for servicing.
Output Ratings
Fuses are rated 2.5A each, PTCs are rated at 2A.
Fire Alarm Disconnect
Supervised Latching or non-latching, individually
selectable for any or all of the eight (8) outputs.
EOL 10K Resistor.
Indicators (LED)
Red LEDs Outputs are triggered (relays energized).
Blue LED FACP disconnect is triggered.
Individual voltage LEDs
Green: 12VDC
Red: 24VDC.
Physical and Environmental
Dimensions (L x W x H)
15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm)..
Product Weight 9.3 lb. (4.2 kg).
Shipping Weight 10.6 lb. (4.8 kg).
Temperature
Operating 0ºC to 49ºC (32ºF to 120ºF).
Storage -20ºC to 70ºC (-4ºF to 158ºF).
Relative Humidity 85% +/-5%.
BTU/Hr. (approx.) 54 BTU/Hr
Specifications
Altronix Corporation | 140 58th St | Brooklyn, NY 11220 USA
phone: +1 718.567.8181 | fax: +1 718.567.9056 | email: info@altronix.com | www.altronix.com
Accessories
NetWay8BT – 802.3bt Managed Midspan
- 8-Port, 480W midspan/injector delivers up to 90W per port
NetWay8BT