Installation Guide

- 8 - Tango8AP(CB) - PoE Driven Multi-Output Power Supply/Charge With Access Power Controller
Tango1B
Terminal/RJ45 Legend Function/Description
PoE+ Data Input IEEE802.3bt Input (Fig. 2b, pg. 4).
Data Output Passes Data to Switch (Fig. 2a, pg. 4)
C FAIL NC Power and Battery Fail (Fig. 2c, pg. 4).
+ 12V – 12VDC output (Fig. 2d, pg. 4).
+ 24V – 24VDC output (Fig. 2e, pg. 4).
+ BAT – Lithium Iron Phosphate battery backup (Fig. 2f, pg. 4).
8-Pin Connector (Fig. 2g, pg. 4) Facilitates electrical connection to PDS8(CB).
PDS8(CB):
Terminal Legend Function/Description
+ INP1 – Factory connected to Tango1B. Do not use these terminals.
+ INP2 – Factory connected to Tango1B. Do not use these terminals.
P [OUT1-OUT8] Positive DC power outputs.
N [OUT1-OUT8] Negative DC power outputs.
ACMS8 and ACMS8CB Access Power Controller
Terminal Legend Function/Description
+ PWR1 Factory connected. Do not use these terminals.
+ PWR2 Factory connected. Do not use these terminals.
+ INP1 through
+ INP8
Eight (8) independently controlled Normally Open (NO), Normally Closed (NC),
Open Collector Sink or Wet Input Triggers.
C, NC
FACP Dry NC output rated 1A/28VDC @ 0.6 Power Factor. Class 2 power-limited.
With EOL JMP intact, will provide 10k resistance in a normal state.
GND, RST
FACP interface latching or non-latching. NO dry input. Class 2 power-limited.
To be shorted for non-latching FACP interface or Latch FACP reset.
GND, EOL
EOL Supervised FACP Input terminals for polarity reversal FACP function.
Class 2 power-limited.
F, + F, R, + R FACP Signaling Circuit Input and Return terminals. Class 2 power-limited.
Output 1 through
Output 8
NO, C, NC, COM
Eight (8) selectable independently controlled outputs [Fail-Safe (NC) or Fail-
Secure (NO)] and eight (8) independently controlled Form “C” Relay outputs.