Installation Guide

Tango8AP(CB) - PoE Driven Multi-Output Power Supply/Charge With Access Power Controller - 3 -
Overview:
Altronix Tango8AP(CB) PoE Driven Multi-Output Power Supply/Charger With Access Power Controller con-
verts an IEEE802.3bt PoE input into eight (8) regulated 24VDC and/or 12VDC outputs and eight (8) protected
24VDC and/or 12VDC outputs up to 65W. It eliminates the need for a high voltage inside of an enclosure.
Tango8AP(CB) is designed to support a single 12VDC LiFePO
4
(Lithium Iron Phosphate) battery for 12VDC
and 24VDC backup.
Specifications:
Inputs:
Tango1B:
802.3bt PoE up to 90W or 802.3at up to 30W or 802.3af up to 15W.
ACMS8/ACMS8CB:
Eight (8) trigger inputs:
a) Normally open (NO) inputs (dry contacts).
b) Normally closed (NC) inputs (dry contacts).
c) Open collector sink inputs.
d) Wet Input (5VDC - 24VDC) with 10K resistor
e) Any combination of the above.
Outputs:
Tango1B:
12VDC up to 5.4A (65W) and/or 24VDC up to 2.7A (65W).
Combined output not to exceed 65W.
When charging batteries:
12VDC up to 4.6A (55W) and/or 24VDC up to 2.3A (55W)
Combined output not to exceed 55W.
• ACMS8:
- Fuse protected outputs rated @ 2.5A per output, non power-limited. Total output 20A max.
ACMS8CB:
- PTC protected outputs rated @ 2A per output, Class 2 power-limited. Total output 16A max.
Do not exceed the individual power supply ratings. See Input/Output Voltage Ratings, pg. 6.
Total output current should not exceed max. current rating of the power supplies employed on each input.
See Maximum Output of Altronix Power Supplies.
Eight (8) selectable independently controlled outputs or eight (8) indepently controlled Form “C” relay outputs
(see below for ratings):
a) Fail-Safe and/or Fail-Secure power outputs.
b) Form “C” relays rated @ 2.5A. 5, 12, 24VDC, 0.6 Power Factor (ACMS8 only).
c) Auxiliary power outputs (unswitched).
d) Any combination of the above.
Individual outputs may be set to OFF position for servicing (output jumper set to middle position).
Does not apply to Dry Contact applications.
Any of the eight (8) fuse/PTC protected power outputs are selectable to follow power Input 1 or Input 2.
Output voltage of each output is the same as the input voltage of the input selected.
See Input/Output Voltage Ratings, pg. 6.
PDS8:
Fuse protected outputs rated @ 3A per output, non power-limited.
PDS8CB:
PTC protected outputs rated @ 2A per output, Class 2 power-limited.
Surge suppression.
Fuse/PTC Ratings:
ACMS8(CB)
- Main input fuses rated 15A/32V each.
- ACMS8: output fuses are rated 3A/32V.
- ACMS8CB: Output PTCs are rated 2A.
• PDS8(CB):
- Main input fuses rated @ 10A/32V each.
- PDS8: output fuses rated @ 3A/32V each.
- PDS8CB: output PTCs rated @ 2A each.
TANGO1B: battery fuse rated @ 10A/32V each.
Ethernet Output (Tango1B):
• Pass-through Ethernet Port (data only).
• 100/1G.