Installation Guide

- 6 - Tango8A(CB) - PoE Driven Access Controller
LED Diagnostics:
Tango1B
LED ON BLINKING
Input Input voltage is present. Input voltage not present.
Battery Normal operating condition. Battery is low or missing.
PoE Indicates Class. Refer to table below Classes 3-8
Supervision PoE Fail or BAT Fail. NC dry contact 30V 1A (not an LED)
Class Green Red Blue Class Green Red Blue
Class 1 Class 5 On Off On
Class 2 Class 6 On Off On
Class 3 Off Off Off Class 7 On On On
Class 4 Off On Off Class 8 On On On
ACMS8 and ACMS8CB Access Power Controller
LED ON OFF
LED 1- LED 8 (Red) Output relay(s) de-energized. Output relay(s) energized.
FACP FACP input triggered (alarm condition). FACP normal (non-alarm condition).
Green Output 1-8 12VDC
Red Output 1-8 24VDC
Terminal Identification:
Tango1B
Terminal/RJ45 Legend Function/Description
PoE+ Data Input IEEE802.3bt Input (Fig. 5b, pg. 7).
Data Output Passes Data to Switch (Fig. 5a, pg. 7)
C FAIL NC Power and Battery Fail (Fig. 5c, pg. 7).
+ 12V – 12VDC output (Fig. 5d, pg. 7).
+ 24V – 24VDC output (Fig. 5e, pg. 7).
+ BAT – Lithium Iron Phosphate battery backup (Fig. 5f, pg. 7).
8-Pin Connector
(Fig. 5g, pg. 7)
Factory connected to ACMS8(CB).
ACMS8 and ACMS8CB Access Power Controller
Terminal Legend Function/Description
+ PWR1 Factory connected to Tango1B. Do not use these terminals.
+ PWR2 Factory connected to Tango1B. Do not use these terminals.
+ INP1 through
+ INP8
Eight (8) independently controlled Normally Open (NO), Normally Closed (NC),
Open Collector Sink or Wet Input Triggers.
C, NC
FACP Dry NC output rated 1A/28VDC @ 0.6 Power Factor. Class 2 power-limited.
With EOL JMP intact, will provide 10k resistance in a normal state.
GND, RST
FACP interface latching or non-latching. NO dry input. Class 2 power-limited.
To be shorted for non-latching FACP interface or Latch FACP reset.
GND, EOL
EOL Supervised FACP Input terminals for polarity reversal FACP function.
Class 2 power-limited.
F, + F, R, + R FACP Signaling Circuit Input and Return terminals. Class 2 power-limited.
Output 1 through
Output 8
NO, C, NC, COM
Eight (8) selectable independently controlled outputs [Fail-Safe (NC) or Fail-
Secure (NO)] and eight (8) independently controlled Form “C” Relay outputs.