Installation Guide
Tango1B - PoE Driven Power Supply with Lithium Battery Backup - 3 -
Fig. 1 - Tango1B configuration
Wiring:
Use 18 AWG or larger for all low voltage power connections.
LED Diagnostics:
LED ON BLINKING
Input Input voltage is present. Input voltage not present.
Battery Normal operating condition. Battery is low or missing.
PoE Indicates Class. Refer to table below Classes 3-8
Supervision PoE Fail or BAT Fail. NC dry contact 30V 1A (not an LED)
PoE Input Class (W) Green Red Blue
Class 1 (3.84) --- --- ---
Class 2 (6.49) --- --- ---
Class 3 (13.00) Off Off Off
Class 4 (25.50) Off On Off
Class 5 (40.00) On Off On
Class 6 (51.00) On Off On
Class 7 (62.00) On On On
Class 8 (71.30) On On On
Terminal Identification:
Terminal/RJ45 Legend Function/Description
PoE+ Data Input IEEE802.3bt Input (Fig. 1b, pg. 3).
Data Output Passes Data to Switch (Fig. 1a, pg. 3)
C FAIL NC
Power and Battery Fail (Fig. 1c, pg. 3). In normal conditions this relay
is closed and in trouble conditions this relay open.
+ 12V – 12VDC output (Fig. 1d, pg. 3).
+ 24V – 24VDC output (Fig. 1e, pg. 3).
+ BAT – Lithium Iron Phosphate battery backup (Fig. 1f, pg. 3).
1a
1b
1c
1d
1e
1f
1g