Spec Sheet
Power Supply/Chargers:
Input
Voltage 120VAC, 60Hz, 4.5A max. (eFlow104NB)
120VAC, 60Hz, 3.5A max. (eFlow102NB)
Input Fuse 6.3A/250V (eFlow104NB)
5A/250V (eFlow102NB)
Output
Voltage 24VDC @ 10A total (eFlow104NB)
12VDC @ 10A total (eFlow102NB)
Auxiliary One (1) Aux outputs rated 1A (unswitched) each
Protection Over-voltage protection. Filtered and regulated.
Both Power Supplies:
Battery Backup
Type Sealed lead acid or gel type.
Fuse Rating 15A/32VDC.
Failover Upon AC loss, instantaneous.
Fire Alarm Disconnect
Supervised Latching or non-latching.
EOL 10K Resistor.
Supervision
AC Failure Form “C” contacts.
Battery Form “C” contacts.
Low DC Power Shutdown
Shuts down DC output terminals if battery voltage drops below
70-75% for 24V units (depending on the power supply).
Prevents deep battery discharge.
Indicators (LED)
AC Input 120VAC is present.
DC Output Powered.
Battery Discharged or not connected.
Three (3) Access Power Controllers (ACM8CB):
Input
Voltage 24VDC from eFlow104NB
Input Fuse 10A/250V.
Outputs
Voltage 24VDC.
Eight (8) 24VDC independently controlled PTC outputs for each ACM8CB
and Four (4) 24VDC independently controlled PTC outputs for ACM4CB:
a) Fail-Safe and/or Fail-Secure power outputs.
b) Auxiliary power outputs (unswitched).
c) Any combination of the above.
Output PTCs 2.5A.
Indicators (LED)
Red LEDs Outputs are triggered (relays energized).
Green LED FACP disconnect is triggered.
One (1) Access Power Controllers (ACM4):
Input
Voltage 24VDC from eFlow104NB
Input Fuse 10A/32V.
Outputs
Voltage 24VDC.
Eight (8) 24VDC independently controlled PTC outputs for each ACM8CB
and Four (4) 24VDC independently controlled PTC outputs for ACM4CB:
a) Fail-Safe and/or Fail-Secure power outputs.
b) Auxiliary power outputs (unswitched).
c) Any combination of the above.
Output PTCs 2.5A.
Indicators (LED)
Red LEDs Outputs are triggered (relays energized).
Green LED FACP disconnect is triggered.
Two (2) Power Distribution Modules (PD16WCB):
Input
Voltage 12VDC from eFlow102NB.
Outputs
Voltage 12VDC.
Output PTCs 2.5A.
Indicators (LED)
Green LED DC Output.
Agency Listings
All components of this Trove kit are UL Listed sub-assemblies.
Please refer to the corresponding Sub-Assembly Installation Guides for
further information.
CE European Conformity.
Physical and Environmental:
Dimensions (H x W x D)
36.12” x 30.125” x 7.06” (917.5mm x 768.1mm x 179.3mm).
Weight (approx.)
Product 85.6 lb. (38.83 kg).
Shipping 98.8 lb. (44.82 kg).
Temperature
Operating 0ºC to 49ºC (32ºF to 120ºF).
Storage -20ºC to 70ºC (-4ºF to 158ºF).
Relative Humidity 85% +/-5%.
BTU/Hr. (approx.): 289 BTU/Hr.
Specifications
T3SSK75F28D
Access & Power Integration Solution