Installation Guide
  - 2 -   Trove ZKTeco Kits
Overview:
Altronix T2ZK7F8 and T2ZK7F16 Trove ZKTeco kits are pre-assembled and consist of Trove enclosures/backplanes with factory installed 
Altronix power supply/chargers and sub-assemblies. 
T2ZK7F8 accommodates up to two (2) ZKTeco modules for up to eight (8) doors in a single enclosure.
T2ZK7F16 accommodates up to four (4) ZKTeco modules for up to sixteen (16) doors in a single enclosure.
Configuration Chart:
Altronix
Model Number
120VAC 60Hz
Input Current (A)
Power Supply Board
Input Fuse Rating
Power Supply Board
Battery Fuse Rating
Maximum Supply
Current for Main and 
Aux. Outputs on 
Power Supply board 
and ACM8 Access 
Power Controllers’ 
outputs
Nominal DC Output 
Voltage
Fail-Safe/Fail-Secure 
or Dry Form “C” 
Outputs
Additional Fused 
Outputs
ACM8 Board 
Input Fuse Rating
ACM8 Board
Output Fuse Rating
PDS8 Board
Input Fuse Rating
PDS8 Board
Output Fuse Rating
[DC] [Aux]
Output 
Range 
(VDC)
Output 
Range 
(VDC)
T2ZK7F8
4.5
6.3A/
250V
15A/
32V
24VDC @ 9.7A
20.17-26.4 20.28-26.4
8
8
10A/
250V
2.5A/
250V
10A/
32V
3A/
32V
T2ZK7F16
24VDC @ 9.4A 16
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local codes and authorities having 
jurisdiction. Product is intended for indoor use only. 
1.  Remove backplane from enclosure. Do not discard hardware.
2.  Mark and predrill holes in the wall to line up with the top two/three keyholes in the enclosure. Install two/three upper fasteners and 
  screws in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the two/three upper screws; 
  level and secure. Mark the position of the lower three holes. Remove the enclosure. Drill the lower holes and install the three 
  fasteners. Place the enclosure’s upper keyholes over the two/three upper screws. Install the three lower screws and make sure to 
  tighten all screws.
3.  Mount included UL Listed tamper switch (Altronix Model TS112 or equivalent) in desired 
  location, opposite hinge. Slide the tamper switch bracket onto the edge of the enclosure 
  approximately 2” from the right side (Fig. 1, pg. 2). Connect tamper switch wiring to the 
  Access Control Panel input or the appropriate UL Listed reporting device. 
  To activate alarm signal open the door of the enclosure.
4.  Mount ZKTeco modules to backplane, refer to pages 3 - 6.
5.  Refer to the eFlow Power Supply/Charger Installation Guide for eFlow104NB and 
 corresponding Sub-Assembly Installation Guides for ACM8, PDS8 and VR6 for 
  further installation instructions. 
Hardware:
Fig. 1
Tamper Switch
(provided)
To Access Control Panel or
UL Listed Reporting Device
Edge of
Enclosure
Enclosure
Nylon Spacer | 5/16” Pan Head Screw | Lock Nut