Spec Sheet
Power Supply 1 (eFlow104NB):
Input
 Voltage   120VAC, 60Hz, 4.5A max.
  Input Fuse  6.5A/250V.
Output
 Voltage   24VDC.
 Current   10A continuous.
Power Supply 2 (eFlow102NB):
Input
 Voltage   120VAC, 60Hz, 3.5A max.
  Input Fuse  5A/250V.
Output
 Voltage   12VDC.
 Current   10A continuous.
Both Power Supplies: 
Outputs
 Auxiliary   Class 2 power-limited @ 1A (unswitched).
 Other   Overvoltage protection. Filtered and regulated.
Battery Backup (not included)
 Type   Sealed lead acid or gel type.
  Fuse Rating  10A / 32VDC.
 Failover  Upon AC loss, instantaneous.
Fire Alarm Disconnect
 Supervised  Latching or non-latching.
 EOL    10K Resistor.
Supervision
  AC Failure  Form “C” contacts.
  Battery  Form “C” contacts.
  Low DC Power Shutdown
 Shuts down DC output terminals if battery voltage drops below 70-75% for 
    24V units or 71-73% for 12V units. Prevents deep battery discharge.
Indicators (LED)
  AC  Input  120VAC is present.
  DC Output  Powered.
Dual Input Power Distribution Module (PDS8):
Input
 Voltage   24VDC from eFlow104NB and 
  12VDC from eFlow102NB.
  Input Fuse  10A/32V.
Outputs
 Voltage   12 or 24VDC individually selectable.
  Output Fuses  3A/32VDC.
Indicators (LED)
  DC  Output  Eight (8) individual output LEDs.
 Green:    12VDC
 Red:      24VDC.
Access Power Controller (ACM8):
Input
 Voltage   24VDC from eFlow104NB.
  Input Fuse  10A/250V.
Outputs
 Voltage   24VDC.
    Eight (8) independently controlled fused outputs:
      a) Fail-Safe and/or Fail-Secure power outputs.
        Form “C” Relays rated 28VAC or VDC @ 2.5A.
      b) Auxiliary power outputs (unswitched).
      c) Any combination of the above.
  Output Fuses  3.5A/250V.
Indicators (LED)
  Red LEDs    Outputs are triggered (relays energized).
  Green  LED  FACP disconnect is triggered.
Access Power Controller (ACM4):
Input
 Voltage      24VDC from eFlow104NB.
  Input Fuse  10A/32V.
Outputs
 Voltage   24VDC.
    Four (4) independently controlled 2.5A outputs:
      a)  Four (4) Fail-Safe and/or Fail-Secure power outputs.
      b)  Four (4) dry form “C” 5A rated relay outputs. 
      c)  Any combination of the above.
    Four (4) auxiliary power outputs (unswitched).
  Output Fuses  3A/32V.
Indicators (LED)
  Red LEDs    Outputs are triggered (relays energized).
  Green  LED  FACP disconnect is triggered.
T2SAK75F12 Kit:
Agency Listings
  All components of this Trove kit are UL Listed sub-assemblies.
  Please refer to the corresponding Sub-Assembly Installation Guides for 
  further information.
 CE    European Conformity.
Physical and Environmental
  Dimensions (H x W x D) 
 27.25” x 21.5” x 6.5” (692.2mm x 546.1mm x 165.1mm).
  Weight (approx.)
 Product   55.4 lbs. (25.1 kg).
 Shipping   60.4 lbs. (27.4 kg).
 Temperature
 Operating  0ºC to 50ºC (32ºF to 122ºF).
 Storage   -20ºC to 70ºC (-4ºF to 158ºF).
  Relative Humidity  85% +/-5%.
  BTU/Hr (approx.):  177 BTU/Hr.
Specifications
T2SAK75F12