Spec Sheet
Input
Voltage 120VAC, 60Hz.
Fusing Varies, see Configuration Reference Chart.
Outputs
Voltage 12 or 24VDC, see Configuration Reference Chart.
Current Varies, see Configuration Reference Chart.
Other Overvoltage protection.
Filtered and regulated.
Back-up Battery (not included)
Capacity 12AH / 12VDC (Up to 4 within enclosure).
40 AH / 65 AH (requires separate enclosure).
Type Sealed lead acid or gel type.
Fuse Rating Varies, see Reference Chart.
Failover Upon AC loss, instantaneous.
Supervision
AC Failure Form “C” contacts.
Battery Form “C” contacts.
Low DC Power Shutdown
Shuts down DC output terminals if battery voltage drops below
71-73% for 12V units and 70-75% for 24V units
(depending on the power supply). Prevents deep battery discharge.
Indicators (LED)
Input 120VAC is present.
DC Output Powered.
Battery Discharged or not connected.
Physical and Environmental
Dimensions (H x W x D)
27.25” x 21.5” x 6.5” (692.2mm x 546.1mm x 165.1mm).
Weight (approx.)
Model Product Weight Shipping Weight
T2MK3F4
39.2 lbs. (17.78 kg) 43 lbs. (19.5 kg)
T2MK3F4Q
39.6 lbs. (18 kg) 43.35 lbs. (19.66 kg)
T2MK3F8
39.6 lbs. (18 kg) 43.35 lbs. (19.66 kg)
T2MK3F8Q
40.0 lbs. (18.15 kg) 43.75 lbs. (19.85 kg)
T2MK7F8
40.1 lbs. (18.19 kg) 43.85 lbs. (19.9 kg)
T2MK7F8Q
40.5 lbs. (18.37 kg) 44.25 lbs. (20.1 kg)
T2MK75F16
41.1 lbs. (18.64 kg) 44.85 lbs. (20.34 kg)
T2MK75F16Q
41.5 lbs. (18.82 klg) 45.25 lbs. (20.5 kg)
T2MK77F16
41.3 lbs. (18.73 kg) 45.05 lbs. (20.43 kg)
T2MK77F16Q
41.7 lbs. (18.9 kg) 45.45 lbs. (20.62 kg)
Temperature
Operating 0ºC to 49ºC (32ºF to 120ºF).
Storage -20ºC to 70ºC (-4ºF to 158ºF).
Relative Humidity 85% +/-5%.
BTU/Hr (approx.):
Model BTU
T2MK3F4, T2MK3F4Q, T2MK3F8, T2MK3F8Q 87
T2MK7F8, T2MK7F8Q 145
T2MK75F16, T2MK75F16Q 217
T2MK77F16, T2MK77F16Q 289
Altronix Corporation | 140 58th St | Brooklyn, NY 11220 USA
phone: +1 718.567.8181 | fax: +1 718.567.9056 | email: info@altronix.com | www.altronix.com
Specifications
Trove / Mercury Kits (fused)
Access & Power Integration Solution
Trove Mercury Kit Configuration Reference Chart
Altronix
Model Number
Nominal DC Output Voltage
Maximum Supply
Current for Main and
Aux. Outputs on
Power Supply board
and ACM4/ACM8
Access Power
Controller’s outputs
Fail-Safe/Fail-
Secure or Dry
Form “C” Outputs
120VAC 60Hz
Input Current (A)
Current Per ACM4/
ACM8 Output (A)
Power Supply Board
Input Fuse Rating
Power Supply Board
Battery Fuse Rating
ACM4/ACM8 Board
Input Fuse Rating
ACM4/ACM8 Board
Output Fuse Rating
PDS8 Board
Input Fuse Rating
PDS8 Board
Output Fuse Rating
PD8UL Board
Output Fuse Rating
Power Supply 1 Power Supply 2
[DC] [Aux] [DC] [Aux]
Output
Range
(VDC)
Output
Range
(VDC)
Output
Range
(VDC)
Output
Range
(VDC)
T2MK3F4
20.19-
26.4
20.19-
26.4
---- ----
24VDC @ 5.8A
4
3.5
2.0
5A/
250V
10A/
32V
10A/
250V
3A/
250V
10A/
250V
3A/
250V
----
T2MK3F4Q
T2MK3F8
8
2.5A/
250V
T2MK3F8Q
T2MK7F8
20.17-
26.4
20.28-
26.4
24VDC @ 9.2A 4.5
6.3A/
250V
15A/
32V
T2MK7F8Q
T2MK75F16
9.7-
13.2
10.03-
13.2
24VDC @ 9.2A
12VDC @ 9.3A
16
8
6.3A/250V
5A/250V
---- ----
3.5A/
250V
T2MK75F16Q
T2MK77F16
20.17-
26.4
20.28-
26.4
24VDC @ 9.2A 9
6.3A/
250V
10A/
250V
3A/
250V
----
T2MK77F16Q