Installation Guide

- 4 - Trove
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, CSA C22.1, Canadian Electrical Code, Part I,
Safety Standard for Electrical Installations, Part I, and with all local codes and authorities having jurisdiction.
Product is intended for indoor use only, within the protected or restricted area.
1. The power supply is pre-wired to the ground (chassis). Connect main incoming ground to the provided green grounding conductor lead.
Connect unswitched AC power (115VAC/120VAC 60Hz) to the terminals marked [L, N] on a single or both power supply boards.
Use 14 AWG or larger for all power connections.
Keep power-limited wiring separate from non power-limited wiring.
Minimum 0.25” spacing must be provided (Figs. 5-12, pgs. 7-14).
CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing equipment.
There are no user serviceable parts inside. Refer installation and servicing to qualified service personnel.
2. Select desired DC output voltage by setting SW1 to the appropriate position on the AL400ULXB2, AL600ULXB, eFlow4NB, and
eFlow6NB power supply (Fig. 2, pg. 4). AL1012ULXB and eFlow102NB power supplies are factory set at 12VDC and
AL1024ULXB2 and eFlow104NB power supplies are factory set at 24VDC.
3. Measure the output voltage of the unit before connecting any devices to ensure proper operation.
Improper or high voltage will damage these devices (Figs. 3d, 4h, pg. 6, Figs. 5-10, pgs. 7-12, Fig. 12, pg. 14).
4. Connect devices or Altronix sub-assembly modules to be powered to the terminals marked [– DC +]
(Figs. 3d, 4h, pg. 6, Figs. 5-10, pgs. 7-12, Fig. 12, pg. 14).
eFlow Power Supply: For auxiliary device connection, this output will not be affected by Low Power Disconnect or Fire
Alarm Interface. Connect device to the terminals marked [+ AUX –] (Fig. 3f, pg. 6, Figs. 5-12, pgs. 7-14).
5. For Access Control applications batteries are optional. Batteries are not optional for ULC-S319. Capacity capable of providing
30 minutes of stand-by is required (See Power Supply Specifications, Pg. 3). When batteries are not used, a loss of AC will result in
the loss of output voltage. When the use of stand-by batteries is desired, they must be lead acid. Connect battery to the terminals
marked [– BAT +]. Use two (2) 12VDC batteries connected in series for 24VDC operation (battery leads included)
(Figs. 3c, 4g, pg. 6, Figs. 5-10, pgs. 7-12, Fig. 12, pg. 14). Use batteries - Casil CL1270 (12V/7AH), CL12120 (12V/12AH) batteries
or UL recognized BAZR2 batteries of an appropriate rating.
6. Connect appropriate signaling notification devices to AC FAIL & BAT FAIL supervisory relay outputs
(Figs. 3b, 4b, pg. 6, Figs. 5-10, pgs. 7-12, Fig. 12, pg. 14).
For eFlow Power Supply/Chargers (steps 7-10):
7. To delay AC reporting for 2 hrs., set dip switch [AC Delay] to OFF position (Fig. 4c, pg. 6, Figs. 5-10, pgs. 7-12, Fig. 12, pg. 14).
To delay AC reporting for 1 min., set dip switch [AC Delay] to ON position (Fig. 4c, pg. 6, Figs. 5-10, pgs. 7-12, Fig. 12, pg. 14).
Note: Must be set to ON position for Burglar Alarm Applications.
8. To enable Fire Alarm Disconnect set dip switch [Shutdown] to ON position (Fig. 4c, pg. 6, Figs. 5-10, pgs. 7-12, Fig. 12, pg. 14).
To disable Fire Alarm Disconnect set dip switch [Shutdown] to OFF position (Fig. 4c, pg. 6, Figs. 5-10, pgs. 7-12, Fig. 12, pg. 14).
9. Trigger terminals are end of a line resistor supervised (10k ohms). Opening or shorting trigger
terminals will cause [DC] output to shutdown (Fig. 4d, pg. 6, Figs. 5-10, pgs. 7-12, Fig. 12, pg. 14).
10. Place a jumper for non-latching FACP. A momentary short on these terminals resets FACP latching
[Trigger EOL Shutdown] (Fig. 4d, pg. 6, Figs. 5-10, pgs. 7-12, Fig. 12, pg. 14).
11. Please ensure that the cover is secured with the provided key lock.
Power Supply Board Output Voltage Settings:
Fig. 2
+ DC ---
SW1
OFF - 24V
ON - 12V
ON
ON
OFF - 24V
ON - 12V
--- DC +
OFF - 24V
ON - 12V
ON
AL400ULXB2/AL600ULXB
Power Supply Board
eFlow4NB/eFlow6NB
Power Supply Board