Installation Guide

Trove - 3 -
Installation Instructions:
1. Remove backplane from enclosure. Do not discard hardware.
2. Mark and predrill holes in the wall to line up with the top two/three keyholes in the enclosure. Install
two/three upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s
upper keyholes over the two/three upper screws; level and secure. Mark the position of the lower
holes. Remove the enclosure. Drill the lower holes and install the two/three fasteners. Place the
enclosure’s upper keyholes over the two/three upper screws. Install the two/three lower screws
and make sure to tighten all screws (refer to enclosure drawings pages 18-20).
3. Mount included UL Listed tamper switch (Honeywell model 112 or equivalent) in desired
location, opposite hinge. Slide the tamper switch bracket onto the edge of the enclosure
approximately 2” from the right side (Fig. 1, pg. 3). Connect tamper switch wiring to
the Access Control Panel input or the appropriate UL Listed reporting device.
To activate alarm signal open the door of the enclosure.
4. Mount boards to backplane, refer to individual Trove installation instructions.
Power Supply Sub-Assembly Specifications:
Altronix
Power Supply
Input Rating Output Rating
Battery Size for
30 min. Backup
Refer to
AL400ULXB2 115VAC, 60Hz, 3.5A 12VDC @ 4A or 24VDC @ 3A 4AH
ULXB Installation Instructions
Rev. ULXB-10182016
AL600ULXB 115VAC, 60Hz, 3.5A 12VDC or 24VDC @ 6A 7AH
AL1012ULXB 115VAC, 60Hz, 2.6A 12VDC @ 10A 12AH
AL1024ULXB2 115VAC, 60Hz, 4.2A 24VDC @ 10A 12AH
eFlow4NB* 120VAC, 60Hz, 3.5A 12VDC or 24VDC @ 4A 4AH
eFlow Installation Instructions
Rev. EFNB-10182016
eFlow6NB* 120VAC, 60Hz, 3.5A 12VDC or 24VDC @ 6A 7AH
eFlow102NB* 120VAC, 60Hz, 3.5A 12VDC @ 10A 12AH
eFlow104NB* 120VAC, 60Hz, 4.5A 24VDC @ 10A 12AH
* LINQ2 can be installed when utilizing eFlow power supply/charger boards.
Sub-Assembly Specifications:
Altronix UL Listed
Sub-Assembly
Description Current Draw Refer to
ACM4(CB)
4 Fused (or PTC) Output
Access Power Controller
12VDC @ 0.4A max. or
24VDC @ 0.2A max.
ACM4/ACM4CB Installation Instructions Rev. 051311
ACM8(CB)
4 Fused (or PTC) Output
Access Power Controller
12VDC @ 0.5A max. or
24VDC @ 0.3A max.
ACM8/ACM8CB Installation Instructions Rev. 042811
MOM5
5 PTC Output Power Distribution
Module with Fire Alarm Interface
12-24VDC 55mA max. MOM5 Installation Instructions Rev. 042811
PD4UL(CB)
4 Fused (or PTC) Output
Power Distribution Module
N/A
PD4UL Installation Instructions IIPD4UL Rev. 051311
PD4ULCB Installation Instructions IIPD4ULCB Rev. 051311
PD8UL(CB)
8 Fused (or PTC) Output
Power Distribution Module
N/A
PD8UL Installation Instructions IIPD8UL Rev. 051311
PD8ULCB Installation Instructions IIPD8ULCB Rev. 051311
PD16W(CB)
16 Fused (or PTC) Output
Power Distribution Module
N/A
PD16W/PD16WCB Installation Instructions
IIPD16W Rev. 051311
PDS8(CB)
8 Fused (or PTC) Dual Input
Power Distribution Module
N/A PDS8/PDS8CB Installation Instructions Rev. 070116
VR6 Voltage Regulator
24VDC @ 1.75A or 3.5A
Output: 5VDC or 12VDC @ 6A
VR6 Installation Instructions Rev. 050517
LINQ2* Network Communication Module 12-24VDC 100mA max. LINQ2 Installation Instructions Rev. 060514
* LINQ2 can be installed when utilizing eFlow power supply/charger boards.
Edge of
Enclosure
to Access Control Panel
or U.L. Listed
Reporting Device
Enclosure
Honeywell
model # 112
Tamper Switch
or equivalent
(provided)
Fig. 1