Spec Sheet

Power Supply (eFlow104NB):
Input
Voltage 120VAC, 60Hz 4.5A.
Input Fuse 6.3A/250V.
Output
Voltage 24VDC @ 10A.
Auxiliary 1A (unswitched).
Protection Overvoltage protection. Filtered and regulated.
Battery Backup (not included)
Type Sealed lead acid or gel type.
Fuse Rating 10A/32VDC.
Failover Upon AC loss, instantaneous.
Fire Alarm Disconnect
Supervised Latching or non-latching.
EOL 10K Resistor.
Supervision
AC Failure Form “C” contacts.
Battery Form “C” contacts.
Low DC Power Shutdown
Shuts down DC output terminals if battery voltage drops below
70-75% for 24V units. Prevents deep battery discharge.
Indicators (LED)
AC Input 120VAC is present.
DC Output Powered.
Battery Discharged or not connected.
Access Power Controller (ACM4):
Input
Voltage 24VDC from eFlow104NB.
Input Fuse 10A/32V.
Outputs
Voltage 24VDC.
Four (4) independently controlled 2.5A outputs:
a) Four (4) Fail-Safe and/or Fail-Secure power outputs.
b) Four (4) dry form “C” 5A rated relay outputs.
c) Any combination of the above.
Four (4) auxiliary power outputs (unswitched).
Output Fuses 3A/32V.
Indicators (LED)
Red LEDs Outputs are triggered (relays energized).
Green LED FACP disconnect is triggered.
Voltage Regulator (VR6):
Input
Voltage 24VDC from eFlow104NB.
Output
Voltage 12VDC.
Current 6A continuous.
Other Surge suppression.
Indicators (LED)
Input 24VDC is present.
Output Powered.
Dual Input Access Power Controller (ACMS8):
Input
Voltage 24VDC from eFlow104NB and 12VDC from VR6.
Main Fuse 15A/32V.
Outputs
Voltage 12 or 24VDC individually selectable.
Eight (8) selectable 12VDC - 24VDC independently controlled
outputs or eight (8) indepently controlled Form “C” relay outputs:
a) Fail-Safe and/or Fail-Secure power outputs.
b) Form “C” Relays. 28VAC or VDC @ 2.5A Rated.
c) Auxiliary power outputs (unswitched).
d) Any combination of the above.
Any of the eight (8) fuse protected power outputs are selectable
to follow power Input 1 or Input 2.
Individual outputs may be set to OFF position for servicing.
Output Fuses 3A/32V.
Indicators (LED)
Red LEDs Outputs are triggered (relays energized).
Blue LED FACP disconnect is triggered.
Individual voltage LEDs:
Green: 12VDC
Red: 24VDC.
Dual Input Power Distribution Module (PDS8):
Input
Voltage 24VDC from eFlow104NB and 12VDC from VR6.
Main Fuse 10A/32V.
Outputs
Voltage 12 or 24VDC individually selectable.
Output Fuses 3A/32V.
Indicators (LED)
DC Output Eight (8) individual output LEDs.
Green: 12VDC
Red: 24VDC.
T2KSK7F12 Kit:
Agency Listings
All components of this Trove kit are UL Listed sub-assemblies.
Please refer to the corresponding Sub-Assembly Installation Guides for
further information.
CE European Conformity.
Physical and Environmental
Dimensions (H x W x D)
27.25” x 21.5” x 6.5” (692.2mm x 546.1mm x 165.1mm).
Weight (approx.)
Product 54.7 lb. (24.8 kg).
Shipping 59.7 lb. (27.1 kg).
Temperature
Operating 0ºC to 50ºC (32ºF to 122ºF).
Storage -20ºC to 70ºC (-4ºF to 158ºF).
Relative Humidity 85% +/-5%.
BTU/Hr (approx.): 131 BTU/Hr.
Specifications
T2KSK7F12
Access & Power Integration Solution