Spec Sheet

Power Supply 1 (eFlow104NB):
Input
Voltage 120VAC, 60Hz, 4.5A max.
Main Fuse 6.5A/250V.
Output
Voltage 24VDC.
Current 10A continuous.
Power Supply 2 (eFlow102NB):
Input
Voltage 120VAC, 60Hz, 3.5A max.
Main Fuse 5A/250V.
Output
Voltage 12VDC.
Current 10A continuous.
Both Power Supplies:
Outputs
Auxiliary Class 2 power-limited @ 1A (unswitched).
Other Overvoltage protection. Filtered and regulated.
Battery Backup (not included)
Type Sealed lead acid or gel type.
Fuse Rating 10A/32VDC.
Failover Upon AC loss, instantaneous.
Fire Alarm Disconnect
Supervised Latching or non-latching.
EOL 10K Resistor.
Supervision
AC Failure Form “C” contacts.
Battery Form “C” contacts.
Low DC Power Shutdown
Shuts down DC output terminals if battery voltage drops below 70-75% for
24V units or 71-73% for 12V units. Prevents deep battery discharge.
Indicators (LED)
AC Input 120VAC is present.
DC Output Powered.
Access Power Controller (ACM8):
Input
Voltage 24VDC from eFlow104NB.
Main Fuse 10A/250V.
Outputs
Voltage 24VDC.
Eight (8) independently controlled fused outputs:
a) Fail-Safe and/or Fail-Secure power outputs.
Form “C” Relays rated 28VAC or VDC @ 2.5A.
b) Auxiliary power outputs (unswitched).
c) Any combination of the above.
Output Fuses 3.5A/250VDC.
Indicators (LED)
Red LEDs Outputs are triggered (relays energized).
Green LED FACP disconnect is triggered.
Access Power Controller (ACM4):
Input
Voltage 24VDC from eFlow104NB.
Main Fuse 10A/32V.
Outputs
Voltage 24VDC.
Four (4) independently controlled 2.5A outputs:
a) Four (4) Fail-Safe and/or Fail-Secure power outputs.
b) Four (4) dry form “C” 5A rated relay outputs.
c) Any combination of the above.
Four (4) auxiliary power outputs (unswitched).
Output Fuses 3A/32V.
Indicators (LED)
Red LEDs Outputs are triggered (relays energized).
Green LED FACP disconnect is triggered.
Power Distribution Module (PD4UL):
Input
Voltage 12VDC from eFlow102NB.
Outputs
Voltage 12VDC.
Four (4) fuse protected outputs.
3.5A per output max.
Output Fuses 3.5A/250V.
Indicators (LED)
Green LED DC Output.
T2AGK75F12 Kit:
Agency Listings
All components of this Trove kit are UL Listed sub-assemblies.
Please refer to the corresponding Sub-Assembly Installation Guides for
further information.
CE European Conformity.
Physical and Environmental
Dimensions (H x W x D)
27.25” x 21.5” x 6.5” (692.2mm x 546.1mm x 165.1mm).
Weight (approx.)
Product 55.5 lb. (25.2 kg).
Shipping 60.5 lb. (27.4 kg).
Temperature
Operating 0ºC to 50ºC (32ºF to 122ºF).
Storage -20ºC to 70ºC (-4ºF to 158ºF).
Relative Humidity 85% +/-5%.
BTU/Hr (approx.): 177 BTU/Hr.
Specifications