Installation Instructions
Overview:
T24150 transformer converts 115VAC 50/60Hz to 24VAC for powering low voltage devices. Maximum power output is rated @ 5.4A.
Specification Chart:
Model # Input (Primary) Output (Secondary)
T24150 115VAC 50/60Hz, 1.2A 24VAC/130VA (5.4A)
Installation Instructions:
1. Mount transformer in desired location/enclosure (refer to Transformer Drawing and Dimensions below).
2. Connect AC power 115VAC, 50/60Hz to primary leads (black and white) from terminal numbers 1 and 2
(refer to Wiring Configuration below).
3. Measure output voltage across the secondary leads (yellow and blue) from terminal numbers 7 and 12 (refer to Wiring Configuration
below) before connecting devices. This helps avoiding potential damage.
Open circuit voltage is approx. 26.1VAC @ 115VAC input.
4. Connect 24VAC device(s) to the secondary leads which are connected to terminals 7 and 12 (refer to Wiring Configuration below).
WARNING: This installation should be made by qualified service personnel and should conform to the National Electrical Code
and all local codes.
Wiring Configuration:
Transformer Drawing and Dimensions:
PRIMARY - 115VAC 50/60Hz SECONDARY - 24VAC
6 5 4 3 2 1 7 8 9 10 11 12
Altronix is not responsible for any typographical errors. Product specifications are subject to change without notice.
140 58th Street, Brooklyn, New York 11220 USA | phone: 718-567-8181 | fax: 718-567-9056
website: www.altronix.com | e-mail: info@altronix.com.
IIT24150 - Rev. 061710 I07U
MEMBER
Secondary Leads
Primary Leads
2.8”
71mm
3.2”
81mm
2.75”
70mm
3”
76mm
2.5”
64mm
2.25”
57mm
1.5”
38mm
3.4”
86mm
T24150
Open Frame Transformer