Installation Instructions

Overview:
T24150 transformer converts 115VAC 50/60Hz to 24VAC for powering low voltage devices. Maximum power output is rated @ 5.4A.
Specification Chart:
Model # Input (Primary) Output (Secondary)
T24150 115VAC 50/60Hz, 1.2A 24VAC/130VA (5.4A)
Installation Instructions:
1. Mount transformer in desired location/enclosure (refer to Transformer Drawing and Dimensions below).
2. Connect AC power 115VAC, 50/60Hz to primary leads (black and white) from terminal numbers 1 and 2
(refer to Wiring Configuration below).
3. Measure output voltage across the secondary leads (yellow and blue) from terminal numbers 7 and 12 (refer to Wiring Configuration
below) before connecting devices. This helps avoiding potential damage.
Open circuit voltage is approx. 26.1VAC @ 115VAC input.
4. Connect 24VAC device(s) to the secondary leads which are connected to terminals 7 and 12 (refer to Wiring Configuration below).
WARNING: This installation should be made by qualified service personnel and should conform to the National Electrical Code
and all local codes.
Wiring Configuration:
Transformer Drawing and Dimensions:
PRIMARY - 115VAC 50/60Hz SECONDARY - 24VAC
6 5 4 3 2 1 7 8 9 10 11 12
Altronix is not responsible for any typographical errors. Product specifications are subject to change without notice.
140 58th Street, Brooklyn, New York 11220 USA | phone: 718-567-8181 | fax: 718-567-9056
website: www.altronix.com | e-mail: info@altronix.com.
IIT24150 - Rev. 061710 I07U
MEMBER
Secondary Leads
Primary Leads
2.8”
71mm
3.2”
81mm
2.75”
70mm
3”
76mm
2.5”
64mm
2.25”
57mm
1.5”
38mm
3.4”
86mm
T24150
Open Frame Transformer

Summary of content (1 pages)