Spec Sheet
T1RM3F4D
Trove / Mercury Kit
Access & Power Integration Solution
Power Supply/Charger (eFlow6NB):
Input
 Voltage   120VAC, 60Hz, 3.5A max.
  Input Fuse  5A / 250V.
Outputs
 Voltage   Factory set at 24VDC.
 Current   6A continuous.
    Maximum Supply Current for Main and Aux. Outputs on
    eFlow6NB Power Supply board, PDS8CB Power Distribution Module’s 
    and ACM4CB Access Power Controller’s outputs is 5.6A.
 Auxiliary   Class 2 power-limited @ 1A (unswitched).
 Other   Overvoltage protection.
  Filtered and regulated.
Battery Backup
 Type   Sealed lead acid or gel type.
  Fuse Rating  10A @ 32VDC.
 Failover    Upon AC loss, instantaneous.
Fire Alarm Disconnect
 Supervised  Latching or non-latching.
 EOL    10K Resistor.
Supervision
  AC Failure   Form “C” contacts.
 Battery   Form “C” contacts.
  Low DC Power Shutdown
 Shuts down DC output terminals if battery voltage drops below 
    70-75% for 24V units. Prevents deep battery discharge.
Indicators (LED)
 Input   120VAC is present.
  DC  Output  Powered.
 Battery   Discharged or not connected.
Power Distribution Module (PDS8CB):
Input
 Voltage   24VDC from eFlow6NB and 12VDC from VR6.
  Input PTC    9A.
Outputs
 Voltage   12 or 24VDC individually selectable.
  Output PTCs  2.5A.
Indicators (LED)
  DC  Output  Eight (8) individual output LEDs.
 Green:    12VDC
 Red:      24VDC.
Voltage Regulator (VR6):
Input
 Voltage   24VDC from eFlow6NB.
Output
 Voltage   12VDC.
 Current   6A continuous.
 Other   Surge suppression.
Indicators (LED)
 Input   24VDC is present.
 Output   Powered.
Access Power Controller (ACM4CB):
Input
 Voltage   24VDC from eFlow6NB.
  Main Fuse   10A / 250V.
Outputs
 Voltage   24VDC.
    Four (4) independently controlled 2.5A outputs:
      a)  Four (4) Fail-Safe and/or Fail-Secure power outputs.
    Four (4) auxiliary power outputs (unswitched).
  Output PTCs  2.5A.
Indicators (LED)
  Red LEDs    Outputs are triggered (relays energized).
  Green  LED  FACP disconnect is triggered.
T1RM3F4D Kit:
Agency Listings
 CE    European Conformity.
Physical and Environmental:
  Dimensions (H x W x D):
 Modular 2U standard EIA 19” rack mount chassis.
 3.25” x 19.0” x 26.5” (82.6mm x 482.6mm x 673.1mm).
 Weights:
 Product    20 lbs. (9.07 kg).
 Shipping   25 lbs. (11.34 kg).
 Temperature
 Operating  0ºC to 49ºC (32ºF to 120ºF).
 Storage   -20ºC to 70ºC (-4ºF to 158ºF).
  Relative Humidity  85% +/-5%.
 BTU/Hr.:   115 BTU/Hr.
Specifications