Installation Instructions

- 2 - Trove Openpath Kits
Overview:
Altronix Trove Openpath kits are pre-assembled and consist of Trove enclosures/backplanes with factory installed Altronix power supply/chargers and sub-
assemblies. These kits also accommodate various combinations of Openpath boards for up to twenty four (24) doors in a single enclosure.
Configuration Chart:
Altronix
Model Number
Power Supply Board
Input Fuse Rating
Power Supply Board
Battery Fuse Rating
120VAC 60Hz
Input Current (A)
Maximum
Supply
Current for
Main and
Aux. Outputs
on Power
Supply board,
ACM4(CB)/
ACM8(CB)
Access Power
Controllers’ or
PDS8(CB)
outputs
Nominal DC
Output Voltage
Fail-Safe/Fail-Secure or
Dry Form “C” Outputs
Additional Fuse or PTC
Protected Outputs
ACM4/ACM4CB Board
Input Fuse Rating
ACM4 Board Output Fuse Rating
ACM4CB Board Output PTC Rating
ACM8(CB) Board Input Fuse Rating
ACM8 Board Output Fuse Rating
ACM8CB Board Output PTC Rating
PDS8 Board Input Fuse Rating
PDS8 Board Output Fuse Rating
PDS8CB Board Input PTC Rating
PDS8 Board Output PTC Rating
Power Supply
[DC] [Aux]
Output
Range
(VDC)
Output
Range
(VDC)
T1PHK1F4S
5A/
250V
15A/
32V
3.5
24VDC @
3.7A
20.17-
26.4
20.28-
26.4
4 8
10A/
32V
3A/
32V
10A/
32V
3A/
32V
T1PHK1F4SD
2.5A 9A 2.5A
T1PHK3F8
3.5
24VDC @
5.9A
20.17-
26.4
20.28-
26.4
8
10A/
250V
2.5A/
250V
T1PHK3F8D
2.5A
T2PHK33F16
7.0
24VDC @
5.9A
+
24VDC @
5.9A
20.17-
26.4
20.28-
26.4
16
2.5A/
250V
T2PHK33F16D
2.5A
T2PHK77F24
6.3A/
250V
15A/
32V
9.0
24VDC @
9.7A
+
24VDC @
9.7A
20.17-
26.4
20.28-
26.4
24
10A/
250V
2.5A/
250V
T2PHK77F24D
2.5A
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local codes and authorities having jurisdiction.
Product is intended for indoor use only.
1. Remove backplane from enclosure. Do not discard hardware.
2. Mark and predrill holes in the wall to line up with the top three keyholes in the enclosure. Install two/three upper fasteners and screws
in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the two/three upper screws; level and secure.
Mark the position of the lower two/three holes. Remove the enclosure. Drill the lower holes and install the fasteners. Place the
enclosure’s upper keyholes over the upper screws. Install the lower screws and make sure to tighten all screws.
3. Mount included UL Listed tamper switch(es) (Altronix Model TS112 or equivalent) in desired location, opposite hinge. Slide the
tamper switch bracket onto the edge of the enclosure approximately 2” from the right side (Fig. 1, pg. 2). Connect tamper switch wiring
to the Access Control Panel input or the appropriate UL Listed reporting device. To activate alarm signal open the door of the enclosure.
4. Mount Openpath boards to backplane, refer to pages 3-6.
5. Refer to the eFlow Power Supply/Charger Installation Guide (eFlow4NB, eFlow6NB, eFlow104NB)
and corresponding Sub-Assembly Installation Guide (ACM4(CB), ACM8(CB), PDS8(CB) and VR6) for
further installation instructions.
Fig. 1
Tamper Switch
(provided)
To Access Control Panel or
UL Listed Reporting Device
Edge of
Enclosure
Enclosure