Installation Guide

StrikeIt4 - 7 -
Fig. 2 - StrikeIt4
Earth Ground
WARNING: To reduce the risk of fire or electric shock, do not expose the unit to rain or moisture.
Replace fuse with the same type and rating: Input Fuse is rated at 5A/250V, Battery PTC rated at 6A.
Wire
Strap
(from
Enclosure
to Door)
Keep power-limited wiring separate from non power-limited. Use minimum 0.25" spacing.
7AH Rechargeable batteries are the largest batteries that can fit in this enclosure
(UL/ULC - Stand-by power only evaluated with 7AH batteries).
A UL Listed external battery enclosure must be used if using 12AH, 40AH or 65AH batteries.
Optional Rechargeable Stand-by
Battery for UL294 Applications.
Note: 12V batteries required for
Canadian installations.
Optional Rechargeable Stand-by
Battery for UL294 Applications.
Note: 12V batteries required for
Canadian installations.
Battery Outputs
(non power-limited)
Class 2
Power-Limited
Outputs
Input
115VAC, 60Hz, 2.5A or
230VAC, 50Hz, 1.5A
(non power-limited)
LGN
OUT1 Timer
OUT2 Timer
Battery Test
IND
FSE
0.5S
DIS
SEQ
FS
1S
24V
OUT1
OUT2
FAI
BAT
AC
AC
GND INP1 GND INP2 GND FACP
ACT-1 ADA-1 Follower 1
ACT-2 ADA-2 Follower 2
ON
--- BAT +
+ OUT2 --- + OUT1 ---
5A 250V
5A 250V
TROUBLE
-- 24V +
-- 12V +
C NC
Supervisory LEDs
DIP
Switches