Installation Guide

- 4 - StrikeIt4
LED Diagnostics:
LED LED Status Panic Device Power Controller Status
Power -
Green (AC)
On Normal operating condition.
Off Loss of AC.
OUT1 - Red
On Output 1 - Energized.
Rapid Blink Output 1 - Short circuit or over-current.
Slow Blink Output 1 - Open circuit
Off Output 1 - De-energized.
OUT2 - Red
On Output 2 - Energized.
Rapid Blink Output 2 - Short circuit or over-current.
Slow Blink Output 2 - Open circuit
Off Output 2 - De-energized.
FAI - Green
On FACP Input triggered (alarm condition).
Off FACP normal (non-alarm condition).
BAT Trouble
Red
Off Battery normal
Slow Blink Bad battery or no battery.
AC Trouble
Green
Off AC normal.
Slow blink AC low or missing.
Maintenance:
Unit should be tested at least once a year for the proper operation as follows:
FACP Supervision: To ensure proper connection and operation of the Fire Alarm disconnect hookup,
remove wire from the terminal marked [FACP] on StrikeIt4. The fire alarm interface
is configurable to either apply 24VDC or disconnect 24VDC from the lock outputs
upon activation. Set as required per application.
With DIP Switch #4 in the OFF position, 24VDC will be disconnected from lock
outputs (DIS mode).
With DIP Switch #4 in the ON position, 24VDC will be applied to the lock outputs
(24V Mode).
Output Voltage Test: Under normal load conditions the DC output voltage should be checked for proper
voltage level.
Battery Test: Under normal load conditions check that the battery is fully charged, check specified
voltage both at battery terminal and at the board terminals marked [– BAT +] to
ensure that there is no break in the battery connection wires.
Depress [Battery Test] button for 5 seconds. If battery is low or missing, the battery
LED will start blinking slowly. It will extinguish when [Battery Test] button is
depressed again with good battery connected or when all power is re-cycled.
Note: Maximum charging current under discharge is 650mA.
Note: Battery life expectancy will vary based on manufacturer and quality of battery.
Note: Expected battery life is 5 years; however, it is recommended changing
batteries in 4 years or less if needed.
Caution: For continuous protection against risk of electric shock and fire hazard, replace
input fuse with the same type and rating: 5A/250V.
Do not expose to rain or moisture. Indoor use only.