Spec Sheet
Input
Voltage 220VAC (working range 198VAC - 256VAC),
60Hz, 4A
Two (2) NO trigger inputs
Fusing Input fuse rating: 6.3A
Outputs
Power options:
- Two (2) 20VDC to 26.4VDC individually controlled lock outputs for
applications with battery back-up. 24VDC for applications without
battery back-up (US applications only)
Current rating 15A for 300ms, 0.75A continuous supply current
- 5V holding voltage with 20VDC to 26.4VDC initial 100ms pulse.
Maximum total 5V holding current of both outputs is 0.74A
One (1) 20VDC to 26.4VDC for applications with battery back-up,
24VDC for applications in US not requiring battery back-up.
Auxiliary output rated @ 0.75A continuous supply current
(Not affected by FACP trigger)
One (1) 12VDC filtered regulated auxiliary output rated @ 0.75A
in alarm, 0.5A stand-by current (Not affected by FACP trigger)
Two (2) follower form “A” SPST relay outputs rated @ 0.6A/28VDC.
Relays energize while input is closed
Two (2) delayed follower Normally Open relay outputs rated @
0.6A/28VDC. Delay time is selectable 0.5 seconds or 1 second
Energized duration is 1 second
Trouble relay output indicating low DC output voltage
Back-up Battery
Type Sealed lead acid or gel type
Failover Upon AC loss, instantaneous
When 7AH batteries are used, battery capacity
for emergency stand-by is 30 minutes.
Fire Alarm Disconnect
Normally Closed FACP trigger input.
Programmable Fire Alarm Disconnect options:
- Removes power to outputs and disables delayed follower relays
- Connects power to lock outputs and enables
delayed follower relays
Indicators (LED)
AC Power (Green) Input voltage is present
Trigger Input (Red) Panic device status/trouble
FAI (Red) FACP disconnect
Battery (Red) Low battery
Physical and Environmental
Dimensions (H x W x D)
13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.6mm).
Enclosure accommodates up to two (2) 12VDC/7AH batteries.
Product Weight 6.25 lb. (2.83 kg)
Shipping Weight 7.15 lb. (3.24 kg)
Temperature
Operating 0ºC to 49ºC (32ºF to 120ºF)
Storage -20ºC to 70ºC (-4ºF to 158ºF)
Relative Humidity 85% +/-5%
BTU/Hr. (approx.): 36 BTU/Hr.
Specifications
Rev. 01032022
StrikeIt1V
Panic Device Power Controller
Altronix StrikeIt1V operates up to two (2) 24VDC panic hardware devices simultaneously. It
is designed to handle the high current surge panic hardware locking devices demand. Each
lock output has an adjustable relock delay timer. It controls a pair of doors simultaneously or
independently control two individual doors. It has a follower relay for each output to trigger
external relays, ADA push plate switches, etc. Delayed follower relays control automatic door
operators for doors that are always locked or for doors that are unlocked during the business
day. In addition, two un-switched auxiliary voltage outputs are provided for powering card
readers, keypads, REX PIRs, electronic timers, relays, etc. A configurable FACP interface will
either provide power or remove power to the lock outputs when activated. LED status indica-
tors are provided to monitor AC power, FACP status and for lock output wiring supervision.
Intelligent logic provides protection against accidental shorting of lock outputs.
StrikeIt1V
(order batteries separately)
Lifetime Warranty
Altronix Corporation | 140 58th St | Brooklyn, NY 11220 USA
phone: +1 718.567.8181 | fax: +1 718.567.9056 | email: info@altronix.com | www.altronix.com