Spec Sheet
Input
 Voltage  220VAC (working range 198VAC - 256VAC), 
  60Hz, 4A
        Two (2) NO trigger inputs
  Fusing  Input fuse rating: 6.3A
Outputs
  Power options:
  -  Two (2) 20VDC to 26.4VDC individually controlled lock outputs for 
    applications with battery back-up. 24VDC for applications without
    battery back-up (US applications only)
    Current rating 15A for 300ms, 0.75A continuous supply current
  -  5V holding voltage with 20VDC to 26.4VDC initial 100ms pulse. 
    Maximum total 5V holding current of both outputs is 0.74A
  One (1) 20VDC to 26.4VDC for applications with battery back-up, 
  24VDC for applications in US not requiring battery back-up.
  Auxiliary output rated @ 0.75A continuous supply current
  (Not affected by FACP trigger)
  One (1) 12VDC filtered regulated auxiliary output rated @ 0.75A 
  in alarm, 0.5A stand-by current (Not affected by FACP trigger)
  Two (2) follower form “A” SPST relay outputs rated @ 0.6A/28VDC. 
  Relays energize while input is closed
  Two (2) delayed follower Normally Open relay outputs rated @ 
  0.6A/28VDC. Delay time is selectable 0.5 seconds or 1 second
  Energized duration is 1 second
  Trouble relay output indicating low DC output voltage
Back-up Battery
 Type  Sealed lead acid or gel type
 Failover  Upon AC loss, instantaneous
  When 7AH batteries are used, battery capacity 
  for emergency stand-by is 30 minutes.
Fire Alarm Disconnect
  Normally Closed FACP trigger input.
  Programmable Fire Alarm Disconnect options:
    -  Removes power to outputs and disables delayed follower relays
    -  Connects power to lock outputs and enables
      delayed follower relays
Indicators (LED)
  AC Power (Green)   Input voltage is present
  Trigger Input (Red)  Panic device status/trouble
  FAI (Red)    FACP disconnect
  Battery (Red)    Low battery
Physical and Environmental
  Dimensions (H x W x D) 
    13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.6mm).
    Enclosure accommodates up to two (2) 12VDC/7AH batteries.
  Product Weight    6.25 lb. (2.83 kg)
  Shipping Weight    7.15 lb. (3.24 kg)
 Temperature
 Operating    0ºC to 49ºC (32ºF to 120ºF)
 Storage    -20ºC to 70ºC (-4ºF to 158ºF)
  Relative Humidity  85% +/-5%
  BTU/Hr. (approx.):  36 BTU/Hr.
Specifications
Rev. 01032022
StrikeIt1V
Panic Device Power Controller
Altronix StrikeIt1V operates up to two (2) 24VDC panic hardware devices simultaneously. It 
is designed to handle the high current surge panic hardware locking devices demand. Each 
lock output has an adjustable relock delay timer. It controls a pair of doors simultaneously or 
independently control two individual doors. It has a follower relay for each output to trigger 
external relays, ADA push plate switches, etc. Delayed follower relays control automatic door 
operators for doors that are always locked or for doors that are unlocked during the business 
day. In addition, two un-switched auxiliary voltage outputs are provided for powering card 
readers, keypads, REX PIRs, electronic timers, relays, etc. A configurable FACP interface will 
either provide power or remove power to the lock outputs when activated. LED status indica-
tors are provided to monitor AC power, FACP status and for lock output wiring supervision. 
Intelligent logic provides protection against accidental shorting of lock outputs.
StrikeIt1V
(order batteries separately)
  Lifetime Warranty
Altronix Corporation | 140 58th St | Brooklyn, NY 11220 USA
phone: +1 718.567.8181 | fax: +1 718.567.9056 | email: info@altronix.com | www.altronix.com

