Installation Guide

- 6 - StrikeIt1V Installation Guide
StrikeIt1V Terminal Identification:
Terminal Legend Function/Description
L, G, N
Connect 220VAC, 50/60 Hz to these terminals: L to Hot, N to Neutral.
+ 12VDC –
12VDC Auxiliary Output @ 0.75A in alarm, 0.5A in stand-by.
+ 24VDC –
24VDC Auxiliary Output @ 0.75A.
20VDC to 26.4VDC for applications with battery back-up.
+ BAT –
24VDC Stand-by Battery Connection (Two (2) 12VDC batteries wired in series).
– OUT 1 +
Connect 24VDC Panic Hardware Device #1 (See compatibility chart for other UL Listed
devices. Operating range of the device must cover 20VDC to 26.4VDC range 0.25 Ohm
maximum wiring resistance).
– OUT 2 +
Connect 24VDC Panic Hardware Device #2. (See compatibility chart for other UL Listed
devices. Operating range of the device must cover 20VDC to 26.4VDC range 0.25 Ohm
maximum wiring resistance).
FACP / GND
Normally Closed Dry Contact from Fire Alarm Control
(100 Ohm maximum wiring resistance).
IN1 / GND
Normally Open Trigger input controls Output 1. May be held closed for extended unlocking
(100 Ohm maximum wiring resistance).
IN2 / GND
Normally Open Trigger input controls Output 2. May be held closed for extended unlocking
(100 Ohm maximum wiring resistance).
Delayed 1
Dry form “A” contacts provide a 1 second momentary pulse after a preset delay. With DIP
switch [SW3] in the OFF position, the delay is 0.5 seconds. With DIP switch [SW3] in the ON
position, the delay is 1 second (Fig. 3b, pg. 9). This permits the Panic Hardware Device to
fully unlock before signaling auto operator to swing door.
Delayed 2
Dry form “A” contacts provide a 1 second momentary pulse after a preset delay. With DIP
switch [SW3] in the OFF position, the delay is 0.5 seconds. With DIP switch [SW3] in the ON
position, the delay is 1 second (Fig. 3b, pg. 9). This permits the Panic Hardware Device to
fully unlock before signaling auto operator to swing door.
Follower 1
Dry form “A” contact. Energizes while output 1 is energized.
Enables outside ADA switch plate to actuate auto operator while door is unlocked.
De-activates outside ADA actuator while door is locked.
Follower 2
Dry form “A” contact. Energizes while output 2 is energized.
Enables outside ADA switch plate to actuate auto operator while door is unlocked.
De-activates outside ADA actuator while door is locked.
Supervision
Indicates low DC output voltage condition.
It may be caused by an AC brownout and low battery occuring simultaneously.
Manual self test needs to be conducted to determine battery condition.
Compatible Panic Hardware Devices:
Manufacturer Model Number
First Choice
3600 - Concealed Vertical Rod Exit Device
3700 - Rim Latching Exit Device
Kawneer EL Paneline Exit Device
Von Duprin
®
EL98 Series Panic Hardware with Electric Latch Retraction
HES 7500 Electric Strike
Maximum Wiring Distance Table:
A maximum 0.25 Ohm resistance of connecting wires is acceptable, see chart below for wire gauge and distances.
Wire Gauge Distance
14 AWG Stranded 40 ft.
12 AWG Stranded 60 ft.
10 AWG Stranded 100 ft.