Installation Guide
StrikeIt1V Installation Guide - 11 -
Maintenance:
Unit should be tested at least once a year for the proper operation as follows:
FACP Supervision: To ensure proper connection and operation of the Fire Alarm disconnect hookup,
remove wire from the terminal marked [FACP] on StrikeIt1V. With the DIP switch
[SW4] in ON positon, unlocked Panic Hardware Devices will unlock. With DIP switch
[SW4] in the OFF position (Fig. 3b, pg. 9), locked Panic Hardware Devices will relock.
Output Voltage Test: Under normal load conditions the DC output voltage should be checked for proper
voltage level.
Battery Test: Under normal load conditions check that the battery is fully charged, check specified
voltage both at battery terminal and at the board terminals marked [+ BAT –] to ensure
that there is no break in the battery connection wires. Press Manual test button.
The battery LED should be illuminated during the self-test (approximately 15 seconds.
When the battery LED blinks slowly, this indicates that the battery is low or missing and
may need to be replaced or serviced.
Note: Maximum charging current under discharge is 650mA.
Note: Expected battery life is 5 years; however it is recommended changing batteries in
4 years or less if needed.
Caution: For continuous protection against risk of electric shock and fire hazard, replace input
fuse with the same type and rating: 6.3A/250V.
Do not expose to rain or moisture; indoor use only.