StrikeIt1 will operate up to two (2) 24VDC panic hardware devices simultaneously. It is
designed to handle the high current surge panic hardware locking devices demand. Each
lock output has an adjustable relock delay timer. It will control a pair of doors simulta-
neously or independently control two individual doors. It has a follower relay for each
output to trigger external relays, ADA push plate switches, etc. Delayed follower relays
control automatic door operators for doors that are always locked or for doors that are
unlocked during the business day. In addition, two un-switched auxiliary voltage outputs
are provided for powering card readers, keypads, REX PIRs, electronic timers, relays,
etc. A configurable FACP interface will either provide power or remove power to the
lock outputs when activated. LED status indicators are provided to monitor AC power,
FACP status and for lock output wiring supervision. Intelligent logic provides protection
against accidental shorting of lock outputs.
Overview
Specifications
StrikeIt1
(order batteries separately)
Input:
• Input115VAC60Hz,6.3amp.
• Two(2)NOtriggerinputs.
• Inputfuserating:6.3amp.
Outputs:
• Poweroptions:
- Two(2)20VDCto26.4VDCindividually
controlled lock outputs for applications with
battery back-up. 24VDC for applications without
battery back-up (US applications only).
Currentrating15ampfor300ms,0.75amp
continuous supply current.
- 5Vholdingvoltagewith20VDCto26.4VDC
initial100mspulse.Maximumtotal5Vholding
currentofbothoutputsis0.74amp.
• One(1)20VDCto26.4VDCforapplicationswith
battery back-up, 24VDC for applications in US not
requiring battery back-up. Auxiliary output rated
@0.75ampcontinuoussupplycurrent
(NotaffectedbyFACPtrigger).
• One(1)12VDCfilteredregulatedauxiliaryoutput
rated@0.75ampinalarm,0.5ampstand-bycurrent
(NotaffectedbyFACPtrigger).
• Two(2)followerform“A”SPSTrelayoutputsrated
@0.6amp/28VDC.Relaysenergizewhile
input is closed.
• Two(2)delayedfollowerNormallyOpenrelay
outputsrated@0.6amp/28VDC.Delaytimeis
selectable0.5secondsor1second.
Energizeddurationis1second.
• TroublerelayoutputindicatinglowDCoutputvoltage.
Battery Backup:
• Batteryleadsincluded.
• Batteryfuserating:25A/32V.
• Maximumchargecurrent650mA.
• Built-inchargerforsealedleadacidorgel
type batteries.
• Automaticswitchovertostand-bybatterywhenACfails.
• When7AHbatteriesareused,batterycapacity
foremergencystand-byis30minutes.
Visual Indicators:
• GreenACPowerLEDindicates115VACpresent.
• RedtriggerinputLEDsindicatepanicdevice
status/trouble(activated,shortoropencircuit).
• GreenFireAlarmInterface(FAI)LEDindicates
FACP disconnect is activated.
• RedBatteryLEDindicateslowbatteryduring
AC failure and manual test.
• GreenACLEDindicateslossofACtrouble
(not active during manual test sequence).
Fire Alarm Disconnect:
• NormallyClosedFACPtriggerinput.
• ProgrammableFireAlarmDisconnectoptions:
- Removes power to outputs and disables delayed
follower relays.
- Connects power to lock outputs and enables
delayed follower relays.
Additional Features:
• Manualtestingtoallowtotestsbatteryconditions.
• Adjustablepanicreleasefrom1sec.to30secs.
Note: Follower and Delay relay turns off when the
potentiometer selected time elapses after release
of the input trigger.
• Camlockincluded.
Electrical:
• Operatingtemperature:0ºCto49ºCambient.
• BTU/Hr.:196.5BTU/Hr.
• SystemACinputVArequirement:218.5VA.
Mechanical:
• EnclosureDimensions(HxWxDapprox.):
13.5”x13”x3.25”
(342.9mmx330.2mmx82.55mm)
• Enclosureaccommodatesuptotwo(2)
12VDC/7AHbatteries.
• Productweight(approx.):6.25lbs.(2.83kg).
• Shippingweight(approx.):7.15lbs.(3.24kg).

Summary of content (2 pages)