Installation Instructions Owner manual
Power Supply Voltage Output Specifications: *
Output VDC Switch Position Max. Load DC
12VDC SW1 - Closed
(Fig. 1b, pg. 3) 4 amp
24VDC SW1 - Open
(Fig. 1b, pg. 3) 4 amp
*Specified at 25˚ C ambient.
Installation Instructions:
The unit should be installed in accordance with The National Electrical Code and all applicable Local Regulations.
1. Mount the unit in desired location.
2. Set SW1 on the power supply board to the desired DC output voltage
(Power Supply Voltage Output Specification Chart).
3.
Connect
A
C po
wer to terminals marked [L & N], connect ground to terminal marked [G] (if used).
Use 18
A
WG or lar
ger for all po
w
er connections (Batter
y, DC output).
Use 22 AWG to 18 AWG for power limited circuits (AC Fail/Low Battery reporting).
SMP5CTX - 1 - - - - .95 / .5 4 13.5”H x 13”W x 3.25”D
SMP5PMCTX - 1 - - - x .95 / .5 4 13.5”H x 13”W x 3.25”D
SMP5PMCTXX - 1 - - - x .95 / .5 4 15.5”H x 12”W x 4.5”D
SMP5PMP4 PD4 4 x - 3.5 x .95 / .5 4 13.5”H x 13”W x 3.25”D
SMP5PMP4CB PD4CB 4 - x 2.5 x .95 / .5 4 13.5”H x 13”W x 3.25”D
SMP5PMP8 PD8
8 x - 3.5 x .95 / .5 4 13.5”H x 13”W x 3.25”D
SMP5PMP8CB PD8CB 8 - x 2.5 x .95 / .5 4 13.5”H x 13”W x 3.25”D
SMP5PMP16 PD16W 16 x - 3.5 x .95 / .5 4 13.5”H x 13”W x 3.25”D
SMP5PMP16CB PD16WCB 16 - x 2.5 x .95 / .5 4 13.5”H x 13”W x 3.25”D
Altronix
Model Number
Accessory Power
Distribution
Module(s)
Number of Outputs
Fused Outputs
PTC Outputs
Indi
vidual Output
Rating (amp)
115VAC/230VAC
Input Current (amp)
12/24VDC Total
Output Current (amp)
Enclosure Dimensions
SMP5CTX Series Power Supply Configuration Reference Chart:
Overview:
These units will convert a 115VAC or 230VAC, 50Hz/60Hz input, into a regulated 12VDC or 24VDC output up to 4
amps of continuous load current (see specifications).
Specifications:
• Universal 115/230VAC input.
• Maximum charge current .5 amp.
• Filtered and electronically regulated outputs.
• Built-in charger for sealed lead acid or gel type batteries.
• Automatic switch over to stand-by battery when
AC fails (zero voltage drop).
• AC input and DC output LED indicators.
• Short circuit and thermal overload protection.
• Complete with power supply, power distribution module
(w
hen applicab
le), enclosure, cam lock & battery leads.
• Power on-off switch.
Supervised Models Only:
• AC fail supervision (form "C" contacts).
• Low battery supervision (form "C" contacts).
- 1 -
SMP5CTX Series
Supervised