Installation Instructions
LED Diagnostics:
Red (DC) Green (AC) Power Supply Status
ON ON Normal operating conditions
ON OFF Loss of AC. Stand-by battery supplying power.
OFF ON No DC output. Short circuit or thermal overload condition.
OFF OFF No DC output. Loss of AC. Discharged or no battery present.
Terminal Identification:
Terminal Legend Function/Description
AC/AC
Low voltage AC input (see voltage output/transformer selection table).
For 6VDC output use 16VAC or higher with 40VA power rating or higher.
For 12VDC output use 16VAC or higher with 85VA power rating or higher.
For 24VDC output use 28VAC with 175VA power rating or higher.
Caution: Do not apply voltage above 28 VAC or 45VDC (maximum input rating).
+ DC – 6VDC,12VDC or 24VDC @ 4A continuous output
+ BAT – Stand-by battery connections. Maximum charge rate 300mA.
STEP 1: Use these holes to mount SMP5 by
pushing the nylon circuit board fasteners(Fig. 1)
through the back of the enclosure.
Nylon fasteners will snap into place.
(Fig. 1)
Nylon Fastener
STEP 2: Mount SMP5 circuit board to nylon fasteners
by pressing down circuit board onto nylon fasteners.
Note: Springlock on fasteners is used to remove
SMP5 circuit board.
Note: Four (4) fasteners are provided in the SMP5 carton.
Springlock
Enclosure Dimensions (H x W x D approximate):
8.5” x 7.5” x 3.5” (215.9mm x 190.5mm x 88.9mm)
+ DC -- + BAT -- AC AC
AC
DC
MADE IN U.S.A.
SW1
6 V 12 V 24 V
SW1 ON OFF OFF
SW2 OFF
OFF ON
SW2
1 2
ON
Altronix is not responsible for any typographical errors. Product specifications are subject to change without notice.
––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
140 58th Street, Brooklyn, New York 11220 USA | phone: 718-567-8181 | fax: 718-567-9056
website: www.altronix.com | e-mail: info@altronix.com | Lifetime Warranty
IISMP5E - Rev. 090710 F18U