Installation Guide
SMP10C12Xseries - 5 -
Terminal Identification:
Power Supply Board
Terminal Legend Function/Description
L, G, N Connect 115VAC to these terminals: L to Hot, N to Neutral.
– DC + 12VDC @ 10 amp continuous outputs.
*AC FAIL
NC,C,NO
Indicates loss of AC power, e.g. connect to audible device or alarm panel. Relay normally
energized when AC power is present. Contact rating 1 amp @ 120VAC / 28VDC
*Low Battery NC,
C,NO
Indicates low battery condition, e.g. connect to alarm panel. Relay normally energized when
DC power is present. Contact rating 1 amp @ 120VAC / 28VDC.
Low battery threshold: 12VDC output threshold set @ approximately 10.5VDC
– BAT + Stand-by battery connections. Maximum charge rate 0.7 amp.
*Note: SupervisedModelsOnly.
PD4/PD4CB/PD8/PD8CB/PD16W/PD16WCB - Power Distribution Module
Terminal Legend
Function/Description
PD4/PD4CB PD8/PD8CB PD16W/PD16WCB
1P to 4P 1P to 8P 1P to16P Positive DC power outputs.