Installation Manual

Overview:
SMP10 power supply/charger converts low voltage AC input into 12VDC or 24VDC @ 10 amp of continuous supply
current (refer to specifications). This general purpose power supply has a wide range of applications for access control,
security and CCTV system accessories that require additional power (Voltage Output/Transformer Selection Table).
Specifications:
Voltage Output/Transformer Selection Table:
Voltage Switch Position Transformer
12VDC @ 10 amp ON 24VAC or 28VAC / 175VA (Altronix model T2428175)
24VDC @ 6 amp OFF 24VAC or 28VAC / 175VA (Altronix model T2428175)
24VDC @ 10 amp OFF 24VAC or 28VAC / 300VA (Altronix model T2428300)
Installation Instructions:
The SMP10 should be installed in accordance with The National Electrical Code and all applicable Local Regulations.
1. Mount the SMP10 in the desired location/enclosure.
2. Connect proper transformer to the terminals marked [AC] (Voltage Output/Transformer Selection Table).
Use 18 AWG or larger for all power connections (Battery, DC output).
3. Set the SMP10 to the desired DC output voltage by setting the switches to the appropriate positions
(Voltage Output/Transformer Selection Table).
Keep power-limited wiring separate from non power-limited wiring (115VAC 50/60Hz Input, Battery Wires).
Minimum 0.25” spacing must be provided.
CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing equipment.
There are no user serviceable parts inside. Refer installation and servicing to qualified service personnel.
4. Measure output voltage before connecting devices. This helps avoiding potential damage.
5. Connect devices to be powered to the terminals marked [+ DC -] (Fig. 1, pg. 2).
6. When the use of stand-by batteries is desired, they must be lead acid or gel type.
Connect battery to the terminals marked [+ BAT -] (battery leads included).
Use two (2) 12VDC batteries connected in series for 24VDC operation.
7. When batteries are not used, a loss of AC will result in the loss of output voltage.
LED Diagnostics:
Red (DC) Green (AC) Power Supply Status
ON ON Normal operating condition.
ON OFF Loss of AC. Stand-by battery supplying power.
OFF ON No DC output. Short circuit or thermal overload condition.
OFF OFF Loss of AC. Discharged or no stand-by battery. No DC output.
SMP10 - Power Supply/Charger
Input:
• Input 28VAC.
(Voltage Output/Transformer Selection Table).
Output:
12VDC or 24VDC selectable output.
10 amp supply current.*
Filtered and electronically regulated outputs.
Short circuit and thermal overload protection.
Battery Backup:
Built-in charger for sealed lead acid or gel type batteries.
Battery Backup (cont’d):
Maximum charge current 0.7 amp.
Zero voltage drop when switching over
to battery backup.
Indicators:
AC input and DC output LED indicators.
Board Dimensions (W x L x H approximate):
4.25” x 7” x 2.125” (108mm x 177.8mm x 54mm).
* Specified at 25˚ C ambient.

Summary of content (2 pages)