Installation Instructions Instruction Manual

LED Diagnostics:
Red (DC) Green (AC) Power Supply Status
ON ON Normaloperatingcondition.
ON OFF LossofAC,Stand-bybatterysupplyingpower.
OFF ON NoDCoutput.Shortcircuitorthermaloverloadcondition.
OFF OFF LossofAC.Dischargedornostand-bybattery.NoDCoutput.
Terminal Identification:
Terminal Function/Description
AC/AC LowvoltageACinput(refer to Voltage Output/Transformer Selection Table).
For12VDCoutputuse24VACor28VACwith175VApowerratingorhigher.
For24VDCoutputuse28VACwith300VApowerratingorhigher.
Caution:Donotapplyvoltagesabove28VAC(28VACismaximuminputrating)
+BAT- Stand-bybatteryconnections.
+DC-- DCoutputvoltagefordevicestobepowered.
AC
DC
OPEN = 24V SW1 CLOSED = 12V
+ BAT --
+ DC --
AC AC
Altronixisnotresponsibleforanytypographicalerrors.Productspecificationsaresubjecttochangewithoutnotice.
14058thStreet,Brooklyn,NewYork11220USA,718-567-8181,fax:718-567-9056
website:www.altronix.com,e-mail:info@altronix.com,LifetimeWarranty,MadeinU.S.A.
IISMP10-Rev.110606  G06K
MEMBER
Fig. 1