Installation Instructions
- 2 - R248 Series
Overview:
Altronix R248 Series Rack Mount CCTV Power Supplies provide 24VAC or 28VAC distributed via eight (8)
fuse or PTC protected outputs for powering CCTV cameras, heaters and other video accessories.
Eight (8) Output R248 Rack Mount Configuration Reference Chart:
Altronix
Model
Number
Output
Voltage
(VAC)
Total
Output
Current
(Power)
Number
of
Outputs
PTC
Protected
Auto-
Resettable
Outputs
Fuse
Protected
Outputs
Individual
Output Current
(max per output -
not to exceed
total output
current)
115VAC,
50/60Hz
Input
Current
R248100
24VAC 4A
8 –
P
3.5A 2.9A
28VAC 3.5A
R248100CB
24VAC 4A
8
P
– 2.5A 2.9A
28VAC 3.5A
R248300
24VAC 14A
8 –
P
3.5A 3A
28VAC 12.5A
R28300CB
24VAC 14A
8
P
– 2.5A 3A
28VAC 12.5A
R248600
24VAC 28A
8 –
P
3.5A 6A
28VAC 25A
R248600CB
24VAC 28A
8
P
– 2.5A 6A
28VAC 25A
Specifications:
Installation Instructions:
1. Mount unit in the desired rack location (Space unit at least 3” from any video monitors).
Do not obstruct side air vents.
2. Set power disconnect circuit breaker to OFF position (Fig. 1c, pg. 3).
3 All units are factory set for 24VAC operation.
For 28VAC operation, adjust unit prior to mounting and applying power as follows:
Change the wire position so that the black wire [28V] is connected to the terminal marked [P] and
the yellow wire [24V] is connected to the terminal marked [S] (Fig. 1, pg. 3).
4. Plug power cord into a grounded 115VAC 50/60 Hz receptacle (Fig. 1b, pg. 3), ground should be connected
as indicated in Fig. 1d, pg. 3.
5. Set power disconnect circuit breaker to RESET (ON) position (Fig. 1c, pg. 3).
6. Measure output voltage before connecting devices. This helps avoiding potential damage.
All terminals with common suffix (P) “1P, 2P...” are the same polarity.
7. Set power disconnect circuit breaker to OFF position (Fig. 1c, pg. 3).
8. Connect devices to the removable terminal blocks marked [1P & 1N] through [8P & 8N] (Fig. 1a, pg. 3).
When wiring is completed on terminal blocks, they can be locked down by tightening screw flanges.
9. Upon completion of wiring, set power disconnect circuit breaker to RESET (ON) position (Fig. 1c, pg. 3).
Input:
• 115VAC, 50/60Hz.
Output:
• Eight (8) fuse or PTC protected outputs.
• 24VAC or 28VAC supply current.
• Outputs are rated @ 3.5A (fuse) or 2.5A (PTC).
• Surge suppression.
Visual Indicators:
• Eight (8) power LEDs.
• Illuminated master power disconnect circuit breaker
with manual reset.
Features:
• Removable terminal blocks with
locking screw flange.
• Spare fuses provided.
• Unit maintains camera synchronization.
Mechanical:
• 2U rack mount chassis for use in standard
EIA 19” rack.
• Enclosure Dimensions (H x W x D approx.):
3.26” x 19.125” x 8.5” (83mm x 486mm x 216mm).