Installation Instructions User Manual

R2432ULseries - 3 -
8. Uponcompletionofthewiring,setpowerdisconnectcircuitbreakertotheRESET(ON)position(Fig. 1c, pg. 3).
9. Green power LEDs on faceplate will illuminate when AC power is present. When an output is in a trouble condition
(blown fuse or tripped PTC) the corresponding LED will not be illuminated (Fig. 1, pg. 3):
a. Blownfuse(R2432300UL&R2432600UL)-SetpowerswitchonthebackoftheunittotheOFFposition
(Fig. 1c, pg. 3). Remove faceplate to access fuses. Replace with fuses rated @ 3.5A/250VA (Altronix model # Fuse1).
b. TrippedPTC(R2432300ULCB&R2432600ULCB)-ToresetPTC,setpowerswitchonthebackoftheunitto
the OFF position. After approximately 30 sec. set power switch to the ON (RESET) position (Fig. 1c, pg. 3).
10. Power switch with built-in circuit breaker:
OFF position - Switch not illuminated. Outputs not powered.
RESET (ON) position - Switch illuminated. Outputs powered.
Circuit breaker tripped - Switch not illuminated. Power LEDs on faceplate are not illuminated. Outputs not powered.
To reset circuit breaker set power switch to the ON (RESET) position (Fig. 1c, pg. 3).
Note: Do not exceed unit’s electrical load ratings as indicated in reference chart (pg. 2).
Do not place mechanical load on the unit.
Unitisdesignedoptimallyfornormaldataroomofficeinstallations.Dataracksshouldalwaysbeproperlyventilated.
CAUTION: Equipment to be installed/serviced by authorized personnel only.
Shut brunch circuit power before servicing/installing equipment.
WARNING: To reduce the risk of fire or electric shock, do not expose the unit to rain or moisture.
This installation should be made by qualified service personnel and should conform
to all local codes and in accordance with the National Electrical Code.
AC Power
LED's
AC Power
LED's
AC Power
LED's
AC Power
LED's
AC Power
LED's
AC Power
LED's
Divider
AC Power
LED's
AC Power
LED's
Removable Terminal
Block
(Green Wire
Earth GND)
PTC1
Used
on PTC
Models
RESET
XFMR*XFMR*
P
N
N
P
Divider
S
S
P
N
N
P
S
S
Illuminated
Power Disconnect
Circuit Breaker with
manual reset
SP N
SP N
24VAC Output
(Factory Set)
28VAC
28VAC
24VAC
24VAC
28VAC Output
Strain Relief
Line Cord
Fig. 1 Fig. 1a
Fig. 1d Fig. 1e
Fig. 1b Fig. 1c