Installation Instructions
Overview:
The PD4ULCB is a UL Listed Sub-Assembly power distribution module, designed to convert a single DC input into
four (4) PTC protected Class 2 Rated power-limited outputs.
Specifications:
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all local
codes and authorities having jurisdiction. Product is intended for indoor use only and should be installed by qualified
personnel.
1. Refer to Sub Assembly Installation Instruction for mounting Rev. MS042511.
2. Connect the desired power supply output to the terminals marked [INPUT] (Fig. 1).
Note: Left terminal is NEG. (-) and right terminal is POS. (+) (Fig. 1).
3. Measure output voltage before connecting devices. This helps avoiding potential damage.
4. Connect devices to be powered to the terminal pairs 1 to 4, marked [1P - 1N] through [4P - 4N].
All terminals with common suffix P “1P, 2P...” are same polarity.
Note: This product is a UL Listed Sub-Assembly for use with Altronix UL Listed power supplies
as indicated in the installation manuals for the power supply.
INPUT
1P 1N 2P 2N
LED
1P, 2P, 3P, 4P = FUSED OUTPUTS
1N, 2N, 3N, 4N = COMMON OUTPUTS
F1
3P 3N 4P 4N
F2 F3 F4
NPS
DC
Positive (+)
Input
DC
Negative ( --- )
Input
Fire Alarm System Power Supply Unit
Also suitable for use as a
Access Control System Unit Subassembly.
9B98
Refer to Installation Instructions
IIPD4ULCB- REV. 030802
Fig. 1
(#P) Positive DC outputs
(#N) Negative DC outputs
Note: DC outputs are power-limited.
Caution: Do not expose to rain
or moisture.
PD4ULCB - UL Listed Sub-Assembly
Power Distribution Module
Altronix is not responsible for any typographical errors.
140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056
website: www.altronix.com, e-mail: info@altronix.com, Lifetime Warranty, Made in U.S.A.
IIPD4ULCB - Rev. 051311 B19N
MEMBER
Agency Listings:
• ULListedSub-AssemblyforAccess
Control System Units (UL 294) and
for Power Supplies for Fire Protective
Signaling Systems (UL 1481).
• cULListed:General Signaling Equipment
Evaluated to CSA Standard C22.2 No.205-M1983
Input:
• 12VDCor24VDCupto10amp.
Outputs:
• Four(4)individuallyPTCprotectedoutputs@2amp
per output max. current (total output current should not
exceed max. current rating of power supply employed).
PTC Ratings:
• PTCsarerated@2A/250V.
Visual Indicators:
• PowerongreenLEDindicator.
Board Dimensions (W x L x H approximate):
3.25” x 5.25” x 1” (82.55mm x 133.35mm x 25.4mm).