Installation Instructions

LOW BAT
NC C NO NC C NO
OFF ON
5A 250V
AC FAIL
--- BAT + --- DC +
15
AC DC
Altronixisnotresponsibleforanytypographicalerrors.Productspecificationsaresubjecttochangewithoutnotice.
14058thStreet,Brooklyn,NewYork11220USA,718-567-8181,fax:718-567-9056
website:www.altronix.com,e-mail:info@altronix.com,LifetimeWarranty,MadeinU.S.A.
IIOLS250-Rev.100509 F27N
MEMBER
Fig. 1
Terminal Identification:
Terminal Legend Function/Description
L, G, N Connect115VACtotheseterminals:LtoHot,NtoNeutral,Gtoground.
--- DC + 24VDC @ 10 amp continuous supply current.
ACFAIL
N.C., C, N.O.
Used to notify loss of AC power, e.g. connect to audible device or alarm panel.
Relay normally energized when AC power is present. Contact rating 1 amp @ 28VDC.
Low Battery
N.C., C, N.O.
Used to indicate low battery condition, e.g. connect to alarm panel. Relay normally energized
when DC power is present. Contact rating 1 amp @ 28VDC.
Lowbatterythreshold:24VDCoutputthresholdset@approximately21VDC.
--- BAT + Stand-bybatteryconnections.Maximumchargerate0.7amp.