Installation Manual

Terminal Identification:
Terminal Legend Function/Description
L, G, N Connect 220VAC to these terminals: L to Hot, N to Neutral, G to ground.
– DC + 12VDC / 24VDC @ 6A continuous output.
AC FAIL
NC, C, NO
Indicates loss of AC power, e.g. connect to audible device or alarm panel. Relay normally energized
when AC power is present. Contact rating 1A @ 28VDC
Low Battery
NC, C, NO
Indicates low battery condition, e.g. connect to alarm panel. Relay normally energized when DC
power is present. Contact rating 1A @ 28VDC.
Low battery threshold:
12VDC output threshold set @ approximately 10.5VDC,
24VDC output threshold set @ approximately 21VDC.
– BAT + Stand-by battery connections. Maximum charge rate 0.5A.
LG N
OFF ON
LOW BAT
NC C NO NC C NO
AC FAIL
--- BAT + --- DC +
AC
DC
5A 250V
OFF - 24V
ON - 12V
ON
Altronix is not responsible for any typographical errors. Product specifications are subject to change without notice.