MaximalF Series Overview:
MaximalF Access Power/Controllers distribute and switch power to access control systems and accessories. They convert a 120VAC
60Hz input into sixteen (16) independently controlled 12VDC or 24VDC fuse protected outputs. These Fail-Safe/Fail-Secure power
outputs may be converted to dry form ā€œCā€ contacts. The outputs are activated by an open collector sink or normally open (NO) dry
trigger input from an Access Control System, Keypad, Push Button, REX PIR, etc. Units will route power to a variety of access control
hardware devices including: Mag Locks, Electric Strikes, Magnetic Door Holders, etc. The FACP Interface enables Emergency Egress,
Alarm Monitoring, or may be used to trigger other auxiliary devices. The fire alarm disconnect feature is individually selectable for
any or all of the sixteen (16) outputs. All interconnecting equipment must be UL Listed.
MaximalF Series Configuration Chart:
Altronix
Model
Number
Nominal DC Output Voltage Options
Maximum Supply Current
for Main and Aux. Outputs
(Power Supply 1/
Power Supply 2)
(amp)
Fuse Protected Outputs
120VAC 60 Hz Input
(current)
Current per ACM8
output (amp)
Power Supply Board
Input Fuse Rating
Power Supply Board
Battery Fuse Rating
ACM8 Board
Input Fuse Rating
Power Supply 1 Power Supply 2
[DC] [AUX] [DC] [AUX]
12VDC Output
Range (volts)
24VDC Output
Range (volts)
12VDC Output
Range (volts)
24VDC Output
Range (volts)
12VDC Output
Range (volts)
24VDC Output
Range (volts)
12VDC Output
Range (volts)
24VDC Output
Range (volts)
Maximal11F
eFlow4NB eFlow4NB ----------
16* 7A 2.5
5A/
250V
7.5A/
32V
10A/
250V
10.1-
13.2
----------
10.05-
13.2
----------
10.1-
13.2
----------
10.05-
13.2
---------- 3.3A + 3.3A
10.1-
13.2
----------
10.05-
13.2
---------- ----------
20.28-
26.4
----------
20.2-
26.4
3.3A + 3.6A
----------
20.28-
26.4
----------
20.2-
26.4
----------
20.28-
26.4
----------
20.2-
26.4
3.6A + 3.6A
Maximal33F
eFlow6NB eFlow6NB ----------
16 7A 2.5
5A/
250V
10A/
32V
10A/
250V
10.0-
13.2
----------
10.03-
13.2
----------
10.0-
13.2
----------
10.03-
13.2
---------- 5.3A + 5.3A
10.0-
13.2
----------
10.03-
13.2
---------- ----------
20.19-
26.4
----------
20.19-
26.4
5.3A + 5.6A
----------
20.19-
26.4
----------
20.19-
26.4
----------
20.19-
26.4
----------
20.19-
26.4
5.6A + 5.6A
Maximal55F
eFlow102NB eFlow102NB
9.3A + 9.3A 16 7A 2.5
5A/
250V
15A/
32V
10A/
250V
10.03-
13.2
----------
10.03-
13.2
----------
10.03-
13.2
----------
10.03-
13.2
----------
Maximal75F
eFlow102NB eFlow104NB
9.3A + 9.6A 16 8A 2.5
5A/250V
(eFlow102NB)
6.3A/250V
(eFlow104NB)
15A/
32V
10A/
250V
10.03-
13.2
----------
10.03-
13.2
---------- ----------
20.17-
26.4
----------
20.28-
26.4
Maximal77F
eFlow104NB eFlow104NB
9.6A + 9.6A 16 9A 2.5 6.3A/250V
15A/
32V
10A/
250V
----------
20.17-
26.4
----------
20.28-
26.4
----------
20.17-
26.4
----------
20.28-
26.4
*Maximal11F only: This unit is classified as Power-Limited stand alone power supply with stand-by battery and it is suitable
to power: sensors, electro-mechanical devices (e.g. electric door strikes).
*Maximal33F, Maximal55F, Maximal75F and Maximal77F: The DC output for these power supplies are not power-limited. If a
power-limited output is required in the end-product application, the DC output from the power supply must be connected to a separately
Listed control unit or accessory board that provides power-limited outputs. The product(s) providing the power-limited output(s) must
be listed as appropriate for the particular end-product application and wired in accordance with the products installation instructions.
Class 1 wiring methods, separation of circuits, and proper fire-rated enclosures all must be considered when connecting the DC output
of the power supply to the end-product devices. The auxiliary outputs of these units are power-limited.
UL Listings for US Installations: UL 294 - UL Listed for Access Control System Units.
UL Listings for Canadian Installations: ULC-S319-05 - Electronic Access Control Systems Class I equipment.
CSA C22.2 No.205 - Signal Equipment.
ULC-S319-05 Electronic Access Control Systems will be invalidated through the use of any add-on, expansion, memory or other
module manufactured by the manufacturer or other manufacturers.