Maximal D Series Single Power Supply Access Power Controllers (fused) Models Include: Maximal3D - 12VDC @ 5A or 24VDC @ 5.4A. - Sixteen (16) PTC protected Class 2 Rated power-limited outputs. Maximal5D - 12VDC @ 9A. - Sixteen (16) PTC protected Class 2 Rated power-limited outputs. Maximal7D - 24VDC @ 9.42A. - Sixteen (16) PTC protected Class 2 Rated power-limited outputs. Installation Guide Altronix Corp. 140 58th St. Brooklyn, NY Rev. MSCB052219 More than just power.
Table of Contents: Maximal D Series Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pg. 3 Maximal D Series Configuration Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pg. 3 Maximal D Series Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pg. 3 Maximal D Installation Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Maximal D Series Overview: Maximal Access Power/Controllers distribute and switch power to access control systems and accessories. They convert a 115VAC 60Hz input into sixteen (16) independently controlled 12VDC or 24VDC Class 2 Rated PTC protected power-limited outputs. The outputs are activated by an open collector sink or normally open (NO) dry trigger input from an Access Control System, Keypad, Push Button, REX PIR, etc.
• Automatic switch over to stand-by battery when AC fails. • Zero voltage drop when unit switches over to battery backup (AC failure condition). • Short circuit and thermal overload protection with auto reset. • Green AC input and red DC output LED indicators on power supply board(s). • AC fail supervision (form “C” contact rated @ 1A/28VDC). • Battery fail and battery presence supervision (form “C” contact rated @ 1A/28VDC). • Enclosure accommodates up to four (4) 12VDC/12AH batteries.
8. 9. 10. 11. 12. (b) Open Collector Sink inputs: Connect the access control panel open collector sink positive (+) to terminals marked [IN] and the negative (–) to terminals marked [GND]. Fire Alarm Interface options (Figs. 8-12, pg. 14): A normally closed [NC] or normally open [NO] input trigger from a fire alarm control panel or a polarity reversal input from an FACP signaling circuit will affect selected outputs.
Maintenance: Unit should be tested at least once a year for the proper operation as follows: FACP Supervision: To ensure proper connection and operation of the Fire Alarm disconnect hookup. Please follow the appropriate procedure below: Normally Open Input: Placing a short between terminals marked [T] and [+ INP] will trigger the Fire Alarm Disconnect. Remove the short to reset. Normally Closed Input: Remove the wire from terminal marked [INP –] will trigger the Fire Alarm Disconnect.
Power Supply Board Terminal Identification: Terminal Legend L, G, N Function/Description Connect 115VAC 60Hz to these terminals: L to hot, N to neutral. + DC – Maximal3D - 12VDC @ 5A or 24VDC @ 5.4A to ACM8CB boards (power-limited) Maximal5D - 12VDC @ 9A to ACM8CB boards (power-limited). Maximal7D - 24VDC @ 9.4A to ACM8CB boards (power-limited). AC FAIL NC, C, NO Indicates loss of AC power.
Power Supply Board Output Voltage Settings: SW1 Fig. 1b + DC --- ON OFF - 24V ON - 12V ON Fig. 1a - Maximal3D Power Supply Board OFF - 24V ON - 12V Access Power Controller Typical Application Diagram (for each ACM8CB): Fig. 2 Fig. 2a Intact = Dry Input Cut = Wet Input Normally Open (N.O.) Door Releasing Device FACP (Fire Alarm Control Panel) FACP Keypad Access Control Panel TRG C Fig.
Fig. 3 - Maximal3D and Maximal5D MAIN Tamper Switch NO C NC FACP +INP- T + RETINTERFACE AC1 N NC C NO NC C NO AC FAIL BAT FAIL AC DC TRIGGER EOL SUPERVISED NO GND RESET +AUX- +INP- T + RETINTERFACE Optional Rechargeable Stand-by Battery for UL294 Applications Note: 12V batteries required Note: 12V batteries required for ULC-S319 installations. for ULC-S319 installations. CAUTION: When power supply board is set for Fig. 3b 12VDC use only one (1) 12VDC stand-by battery.
AC DC OFF - 24V ON - 12V SUPERVISED TRIGGER EOL GND RESET NO +AUX- +INP- T + RETINTERFACE BAT FAIL NO C NC FACP AC FAIL NC C NO NC C NO Tamper Switch + + Power Control AC1 Power Supply Board Neutral +INP- T + RETINTERFACE N NO C NC FACP G Optional Rechargeable Stand-by Battery MAIN MAIN Edge of Enclosure + + Power Control L Fig.
NEC Power-Limited Wiring Requirements for Maximal3D: Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits. One such example of this is shown below. Your specific application may require different conduit knockouts to be used.
NEC Power-Limited Wiring Requirements for Maximal5D: Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits. One such example of this is shown below. Your specific application may require different conduit knockouts to be used.
NEC Power-Limited Wiring Requirements for Maximal7D: Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits. One such example of this is shown below. Your specific application may require different conduit knockouts to be used.
FACP Hook-Up Diagrams: Fig. 8 Polarity reversal input from FACP signaling circuit output (polarity is referenced in alarm condition): CUT JUMPER FACP FACP OUTPUT EOL -- FROM FACP OUTPUT + CIRCUIT NO C NC FACP INTERFACE TRG Fig. 9 Normally Open: Non-Latching FACP trigger input: Fig. 11 Normally Open FACP Latching trigger input with reset (This output has not been evaluated by UL): FACP TRG N.O. TRIGGER INPUT N.O. TRIGGER INPUT N.C.
Notes: Maximal3D/Maximal5D/Maximal7D Access Power Controllers (PTC) Installation Guide - 15 -
Enclosure Dimensions (H x W x D approximate): 26” x 19” x 6.25” (660.4mm x 482.6mm x 158.8mm) 19” (482.6mm) 4” (101.6mm) 7” (177.8mm) 4” (101.6mm) 2” (50.8mm) 6.25” (158.8mm) 2” (50.8mm) 19” (482.6mm) 8.9” (226.1mm) 8.4” (213.4mm) 0.85” (21.6mm) 7” (177.8mm) 8.5” (215.9mm) 8.4” (213.4mm) 0.85” (21.6mm) 1.25” (31.75mm) 2” (50.8mm) 1” (25.4mm) 8.9” (226.1mm) 6.25” (158.8mm) 0.85” (21.6mm) 26” (660.4mm) 7” (177.8mm) 4” (101.6mm) 26” (660.4mm) 1.0” (25.4mm) 7.5” (190.