Access Power Controllers Series Installation Guide Models Include: Maximal3D - 12VDC @ 5A or 24VDC @ 5.4A. - Sixteen (16) PTC protected Class 2 Rated power-limited outputs. Maximal5D - 12VDC @ 9A. - Sixteen (16) PTC protected Class 2 Rated power-limited outputs. Maximal7D - 24VDC @ 9.4A. - Sixteen (16) PTC protected Class 2 Rated power-limited outputs. Altronix Corp. 140 58th St. Brooklyn, NY Rev. SCB110912 More than just power.
Table of Contents: MaximalD Series Overview.............................................................................................. 3 MaximalD Series Configuration Chart.............................................................................. 3 MaximalD Series Features................................................................................................ 3 MaximalD Installation Instructions................................................................................ 4-5 Maintenance...
MaximalD Series Overview: Maximal Access Power/Controllers distribute and switch power to access control systems and accessories. They convert a 115VAC 60Hz input into sixteen (16) independently controlled 12VDC or 24VDC Class 2 Rated PTC protected powerlimited outputs. These Fail-Safe/Fail-Secure power outputs may be converted to dry form “C” contacts.
MaximalD Installation Instructions: Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local codes and authorities having jurisdiction. Product is intended for indoor use only. Power Supply Board LED Diagnostics (pg. 5) Access Power Controller LED Diagnostics (pg. 6) Power Supply Board Terminal Identification (pg. 6) Access Power Controller Terminal Identification (pg. 6) Power Supply Board Stand-by Battery Specifications (pg.
9. FACP Dry form “C” output (Fig. 2b, pg. 8): FACP form “C” contacts can be use to trigger reporting or signaling devices. These contact switch upon a fire alarm input trigger to the ACM8CB boards. 10. Stand-by Battery Connections (Figs. 3-7, pgs. 9-13): For Access Control applications batteries are optional. If batteries are not used a loss of AC will result in the loss of output voltage. Batteries must be lead acid or gel type.
Power Supply Board LED Diagnostics: Red (Bat) ON OFF Battery Status Normal operating condition. Battery fail/low battery. Access Power Controller LED Diagnostics: LED LED 1- LED 8 (Red) Trg (Green) ON Output relay(s) energized. FACP input triggered (alarm condition). OFF Output relay(s) de-energized. FACP normal (non-alarm condition). Power Supply Board Terminal Identification: Terminal Legend L, N + DC - Function/Description Connect 115VAC 60Hz to these terminals: L to hot, N to neutral.
Power Supply Board Stand-by Battery Specifications: Altronix Model: Power Supply Board 20 Min. of Backup 4 hr. of Backup 24 hr. of Backup N/A 5.0A N/A N/A 5.4A 0.7A 12VDC/12AH 9.0A Battery capacity for emergency stand-by at least 20 min. N/A 24VDC/12AH 7.7A 1.2A 200mA 24VDC/65AH* N/A 7.7A 1.2A Battery AL600ULXB 12VDC/40AH* Maximal3D (Refer to Fig. 1a, pg.
Access Power Controller Typical Application Diagram (for each ACM8CB): Fig. 2 Fig. 2a Intact = Dry Input Cut = Wet Input Normally Open (N.O.
Fig.
- 10 - 12VDC Rechargeable Battery** (Optional) 12VDC Rechargeable Battery** (Optional) LED5 LED7 10A 250V 4 J2 J1 NC C NO COM NC C NO COM OUTPUT 7 OUTPUT 8 J3 LED8 3 NO C NC + INP --- T + RET FACP INTERFACE MAIN LED2 NC C NO COM NC C NO COM OUTPUT 1 OUTPUT 2 LED1 LED4 F4 NC C NO COM NC C NO COM OUTPUT 3 OUTPUT 4 LED3 F3 IN GND IN GND IN GND IN GND 1 2 3 4 LED5 LED6 F6 NC C NO COM NC C NO COM OUTPUT 5 OUTPUT 6 F5 IN GND IN GND IN GND IN GND 8 5 6 7 Neutral NC C NO COM NC C NO COM O
NEC Power-Limited Wiring Requirements for Maximal3D: Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits. One such example of this is shown below. Your specific application may require different conduit knockouts to be used.
NEC Power-Limited Wiring Requirements for Maximal5D: Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits. One such example of this is shown below. Your specific application may require different conduit knockouts to be used.
NEC Power-Limited Wiring Requirements for Maximal7D: Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits. One such example of this is shown below. Your specific application may require different conduit knockouts to be used.
FACP Hook-Up Diagrams: Fig. 8 Polarity reversal input from FACP signaling circuit output (polarity is referenced in alarm condition): CUT JUMPER FACP OUTPUT EOL -- FROM FACP OUTPUT + CIRCUIT NO C NC FACP INTERFACE TRG Fig. 10 Normally Open FACP Latching trigger input with reset: (This output has not been evaluated by UL) TRG N.O. TRIGGER INPUT N.O. TRIGGER INPUT NO C NC FACP INTERFACE Fig. 11 Normally Closed - Non-Latching FACP trigger input: TRG - 14 - N.C.
Enclosure Dimensions (H x W x D approximate): 26” x 19” x 6.25” (660.4mm x 482.6mm x 158.75mm) 19” (482.6mm) 2” (50.8mm) 4” (101.6mm) 7” (177.8mm) 4” (101.6mm) 2” (50.8mm) 6.25” (158.75mm) TOP 1.25” (31.75mm) 0.85” (21.59mm) 19” (482.6mm) 8.9” (226.06mm) 1.25” (31.75mm) 0.85” (21.59mm) 8.4” (213.36mm) 1.5” (38.1mm) 1.5” (38.1mm) 1.5” (38.1mm) 5” (127mm) 8.5” (215.9mm) 7” (177.8mm) 7.5” (190.5mm) 7.5” (190.5mm) 26” (660.4mm) 8.5” (215.9mm) 26” (660.4mm) 26” (660.
Notes: Altronix is not responsible for any typographical errors. 140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056 web site: www.altronix.com, e-mail: info@altronix.com. Lifetime Warranty, Made in U.S.A.