Installation Guide
Maximal11F/Maximal33F/Maximal55F/Maximal77F/Maximal75F Access Power Controllers (Fused) - 6 -
Access Power Controller Terminal Identification:
Terminal Legend Function/Description
-- Power +
12VDC or 24VDC from power supply/charger (factory connected).
These terminals are paralleled to the - Control + terminals.
-- Control +
These terminals are paralleled to the - Power + terminals.
These terminals can be connected to an external Listed power-limited access control power supply to provide
isolated operating power for the devices (Not evaluated by UL) (jumpers J1 and J2 must be removed).
TRIGGER
INPUT 1-INPUT 8
IN, GND
From normally open and/or open collector sink trigger inputs
(request to exit buttons, exit pir’s, etc.)
OUTPUT 1-
OUTPUT 8
NC, C, NO, COM
12VDC to 24VDC trigger controlled outputs. Maximum load per output is 2.5 amp.
Maximal11F: P/S 1 - 10.1-13.2VDC @ 3.3 amp P/S 2 - 10.1-13.2VDC @ 3.3 amp or
P/S 1 - 20.28-26.4VDC @ 3.6 amp P/S 2 - 20.28-26.4VDC @ 3.6 amp or
P/S 1 - 10.1-13.2VDC @ 3.3 amp and P/S 2 - 20.28-26.4VDC @ 3.6 amp.
Maximal33F: P/S 1 - 10.0-13.2VDC @ 5.3 amp P/S 2 - 10.0-13.2VDC @ 5.3 amp or
P/S 1 - 20.28-26.4VDC @ 5.6 amp P/S 2 - 20.28-26.4VDC @ 5.6 amp or
P/S 1 - 10.0-13.2VDC @ 5.3 amp and P/S 2 - 20.28-26.4VDC @ 5.6 amp.
Maximal55F: P/S 1 - 10.03-13.2VDC @ 9.3 amp and P/S 2 - 10.03-13.2VDC @ 9.3 amp.
Maximal75F: P/S 1 - 10.03-13.2VDC @ 9.3 amp and P/S 2 - 20.17-26.4VDC @ 9.6 amp.
Maximal77F: P/S 1 - 20.17-26.4VDC @ 9.6 amp and P/S 2 - 20.17-26.4VDC @ 9.6 amp.
Fail-Safe [NC positive (+) & COM Negative (-)], Fail-Secure [NO positive (+) & COM Negative (-)],
Auxiliary output [C positive (+) & COM Negative (-)] (When using AC power supplies polarity needs not
to be observed), NC, C, NO convert to dry form “C” 5 amp 24VAC/VDC rated dry outputs when fuses are
removed. Contacts shown in a non-triggered state.
FACP INTERFACE
T, + INPUT --
Fire Alarm Interface trigger input from FACP. Trigger inputs can be normally open,
normally closed from an FACP signaling circuit output (Figs. 5-9, pg. 10).
FACP INTERFACE
NC, C, NO