Access Power Controllers Series Installation Guide Models Include: Maximal3 - 12VDC @ 5A or 24VDC @ 5.4A. - Sixteen (16) fuse protected non power-limited outputs. Maximal5 - 12VDC @ 9A. - Sixteen (16) fuse protected non power-limited outputs. Maximal7 - 24VDC @ 9.4A. - Sixteen (16) fuse protected non power-limited outputs. Altronix Corp. 140 58th St. Brooklyn, NY Rev. SF110912 More than just power.
Table of Contents: Maximal Series Overview................................................................................................. 3 Maximal Series Configuration Chart................................................................................ 3 Maximal Series Features................................................................................................... 3 Maximal Installation Instructions...................................................................................
Maximal Series Overview: Maximal Access Power/Controllers distribute and switch power to access control systems and accessories. They convert a 115VAC 60Hz input into sixteen (16) independently controlled 12VDC or 24VDC fuse protected outputs. These Fail-Safe/ Fail-Secure power outputs may be converted to dry form “C” contacts. The outputs are activated by an open collector sink or normally open (NO) dry trigger input from an Access Control System, Keypad, Push Button, REX PIR, etc.
Maximal Installation Instructions: Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local codes and authorities having jurisdiction. Product is intended for indoor use only. Power Supply Board LED Diagnostics (pg. 5) Access Power Controller LED Diagnostics (pg. 6) Power Supply Board Terminal Identification (pg. 6) Access Power Controller Terminal Identification (pg. 6) Power Supply Board Stand-by Battery Specifications (pg.
(c) FACP Signaling Circuit input trigger: Connect the positive (+) and negative (-) from the FACP signaling circuit output to the terminals marked [+ INP -]. Connect the FACP EOL to the terminals marked [+ RET -] (polarity is referenced in an alarm condition). Jumper located next to TRG LED must be cut (Fig. 2a, pg. 5, Fig. 8, pg. 14). 9. FACP Dry form “C” output (Fig. 2b, pg. 8): FACP form “C” contacts can be use to trigger reporting or signaling devices.
Power Supply Board LED Diagnostics (cont’d): Red (Bat) ON OFF Battery Status Normal operating condition. Battery fail/low battery. Access Power Controller LED Diagnostics: LED LED 1- LED 8 (Red) Trg (Green) ON Output relay(s) energized. FACP input triggered (alarm condition). OFF Output relay(s) de-energized. FACP normal (non-alarm condition). Power Supply Board Terminal Identification: Terminal Legend L, G, N + DC -- Function/Description Connect 115VAC 60Hz to these terminals: L to hot, N to neutral.
Power Supply Board Stand-by Battery Specifications: Altronix Model: Battery 20 Min. of Backup 4 hr. of Backup 24 hr. of Backup 12VDC/40AH* N/A 5.0A N/A 24VDC/40AH* N/A 5.4A 0.7A 12VDC/12AH 9.0A Battery capacity for emergency stand-by at least 20 min. N/A 24VDC/12AH 7.7A 1.2A 200mA 24VDC/65AH* N/A 7.7A 1.2A Power Supply Board AL600ULXB Maximal3 (Refer to Fig. 1a, pg.
Access Power Controller Typical Application Diagram (for each ACM8): Fig. 2 Fig. 2a Intact = Dry Input Cut = Wet Input Normally Open (N.O.) Door Releasing Device FACP Keypad Access Control Panel TRG (Fire Alarm Control Panel) C NO F1 F2 F3 IN GND IN GND IN GND IN GND 5 6 7 8 F4 F5 F6 F7 F8 ON ON 2 3 4 1 2 3 4 SW1-SW8 FACP Interface ON 1 1 NO C NC + INP --- T + RET FACP INTERFACE TRG IN GND IN GND IN GND IN GND 1 2 3 4 Fig.
Fig.
LED2 F2 NC C NO COM NC C NO COM OUTPUT 3 OUTPUT 4 NC C NO COM NC C NO COM OUTPUT 5 OUTPUT 6 LED6 LED7 2 10A 250V 4 J2 J1 3 MAIN LED2 NC C NO COM NC C NO COM OUTPUT 1 OUTPUT 2 LED1 F2 LED4 F4 NC C NO COM NC C NO COM OUTPUT 3 OUTPUT 4 LED3 F3 IN GND IN GND IN GND IN GND 1 2 3 4 LED5 LED6 F6 NC C NO COM NC C NO COM OUTPUT 5 OUTPUT 6 F5 IN GND IN GND IN GND IN GND 5 6 7 8 LED7 F7 J3 LED8 F8 1 ON 2 3 4 TRG 1 ON 2 10A 250V 4 J2 J1 3 --- BAT + NC C NO COM NC C NO COM O
NEC Power-Limited Wiring Requirements for Maximal3: Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits. One such example of this is shown below. Your specific application may require different conduit knockouts to be used.
NEC Power-Limited Wiring Requirements for Maximal5: Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits. One such example of this is shown below. Your specific application may require different conduit knockouts to be used.
NEC Power-Limited Wiring Requirements for Maximal7: Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits. One such example of this is shown below. Your specific application may require different conduit knockouts to be used.
FACP Hook-up Diagrams: Fig. 8 Polarity reversal input from FACP signaling circuit output (polarity is referenced in alarm condition): FACP OUTPUT EOL -- FROM FACP OUTPUT + CIRCUIT NO C NC FACP TRG INTERFACE CUT JUMPER Fig. 10 Normally Open FACP Latching trigger input with reset: (This output has not been evaluated by UL) TRG N.O. TRIGGER INPUT N.O. TRIGGER INPUT NO C NC FACP INTERFACE Fig. 11 Normally Closed - Non-Latching FACP trigger input: TRG - 14 - N.C.
Enclosure Dimensions (H x W x D approximate): 26” x 19” x 6.25” (660.4mm x 482.6mm x 158.75mm) 19” (482.6mm) 2” (50.8mm) 4” (101.6mm) 7” (177.8mm) 4” (101.6mm) 2” (50.8mm) 6.25” (158.75mm) TOP 1.25” (31.75mm) 0.85” (21.59mm) 19” (482.6mm) 8.9” (226.06mm) 1.25” (31.75mm) 0.85” (21.59mm) 8.4” (213.36mm) 1.5” (38.1mm) 1.5” (38.1mm) 1.5” (38.1mm) 5” (127mm) 8.5” (215.9mm) 7” (177.8mm) 7.5” (190.5mm) 7.5” (190.5mm) 26” (660.4mm) 8.5” (215.9mm) 26” (660.4mm) 26” (660.