Installation Guide

Maximal11FD/Maximal33FD/Maximal55FD/Maximal77FD/Maximal75FD Access Power Controllers (PTC) - 2 -
MaximalFD Series Overview:
MaximalFD Access Power/Controllers distribute and switch power to access control systems and accessories. They convert a 120VAC
60Hz input into sixteen (16) independently controlled 12VDC or 24VDC PTC protected outputs. Outputs are activated by an open col-
lector sink or normally open (NO) dry trigger input from an Access Control System, Card Reader, Keypad, Push Button, PIR, etc. Units
will route power to a variety of access control hardware devices including: Mag Locks, Electric Strikes, Magnetic Door Holders, etc.
Outputs will operate in both Fail-Safe and/or Fail-Secure modes. The FACP Interface enables Emergency Egress, Alarm Monitoring,
or may be used to trigger other auxiliary devices. The fire alarm disconnect feature is individually selectable for any or all of the eight
(8) outputs.
MaximalFD Series Configuration Chart:
Altronix
Model
Number
Nominal DC Output Voltage Options
Maximum Supply Current
for Main and Aux. Outputs
(Power Supply 1/
Power Supply 2)
(amp)
PTC Protected
Power-limited Outputs
120VAC 60 Hz Input
(current)
Current per ACM8CB
output (amp)
Power Supply Board
Input Fuse Rating
Power Supply Board
Battery Fuse Rating
Power Supply 1 Power Supply 2
[DC] [AUX] [DC] [AUX]
12VDC Output
Range (volts)
24VDC Output
Range (volts)
12VDC Output
Range (volts)
24VDC Output
Range (volts)
12VDC Output
Range (volts)
24VDC Output
Range (volts)
12VDC Output
Range (volts)
24VDC Output
Range (volts)
Maximal11FD
eFlow4NB eFlow4NB ----------
16 7A 2
5A/
250V
7.5A/
32V
9.8-
13.2
----------
10.05-
13.2
----------
9.8-
13.2
----------
10.05-
13.2
---------- 3.3A + 3.3A
9.8-
13.2
----------
10.05-
13.2
---------- ----------
19.9-
26.4
----------
20.2-
26.4
3.3A + 3.6A
----------
19.9-
26.4
----------
20.2-
26.4
----------
19.9-
26.4
----------
20.2-
26.4
3.6A + 3.6A
Maximal33FD
eFlow6NB eFlow6NB ----------
16 7A 2
5A/
250V
10A/
32V
9.7-
13.2
----------
10.03-
13.2
----------
9.7-
13.2
----------
10.03-
13.2
---------- 5.3A + 5.3A
9.7-
13.2
----------
10.03-
13.2
---------- ----------
19.8-
26.4
----------
20.19-
26.4
5.3A + 5.6A
----------
19.8-
26.4
----------
20.19-
26.4
----------
19.8-
26.4
----------
20.19-
26.4
5.6A + 5.6A
Maximal55FD
eFlow102NB eFlow102NB
9.3A + 9.3A 16 7A 2
5A/
250V
15A/
32V
9.7-
13.2
----------
10.03-
13.2
----------
9.7-
13.2
----------
10.03-
13.2
----------
Maximal75FD
eFlow102NB eFlow104NB
9.3A + 9.6A 16 8A 2
5A/250V
(eFlow102NB)
6.3A/250V
(eFlow104NB)
15A/
32V
9.7-
13.2
----------
10.03-
13.2
---------- ----------
19.8-
26.4
----------
20.28-
26.4
Maximal77FD
eFlow104NB eFlow104NB
9.6A + 9.6A 16 9A 2 6.3A/250V
15A/
32V
----------
19.8-
26.4
----------
20.28-
26.4
----------
19.8-
26.4
----------
20.28-
26.4
All units: These unit are classified as Power-Limited stand alone power supplies with stand-by battery and they are suitable
to power: sensors, electro-mechanical devices (e.g. electric door strikes).
* UL Listings for US Installations: UL 294 - UL Listed for Access Control System Units.
UL Listings for Canadian Installations: ULC-S319-05 - Electronic Access Control Systems Class I equipment.
CSA C22.2 No.205 - Signal Equipment.
ULC-S319-05 Electronic Access Control Systems will be invalidated through the use of any add-on, expansion, memory or other
module manufactured by the manufacturer or other manufacturers.