Spec Sheet

Power Supply (eFlow104NB):
Input
Voltage 120VAC, 60Hz, 4.5A max.
Input Fuse 6.3A/250V.
Outputs
Voltage 24VDC @ 10A.
Auxiliary 1A (unswitched).
Protection Overvoltage protection.
Filtered and regulated.
Battery Backup
Type Sealed lead acid or gel type.
Fuse Rating 10A @ 32VDC.
Failover Upon AC loss, instantaneous.
Fire Alarm Disconnect
Supervised Latching or non-latching.
EOL 10K Resistor.
Supervision
AC Failure Form “C” contacts.
Battery Form “C” contacts.
Low DC Power Shutdown
Shuts down DC output terminals if battery voltage drops below
70-75% for 24V units (depending on the power supply).
Prevents deep battery discharge.
Indicators (LED)
AC Input 120VAC is present.
DC Output Powered.
Battery Discharged or not connected.
Power Distribution Module (PD8UL):
Input
Voltage 24VDC from eFlow104NB.
Outputs
Voltage 24VDC.
Eight (8) fuse protected outputs.
3.5A per output max.
Output Fuses 3.5A / 32VDC.
Indicators (LED)
Green LED DC Output.
Access Power Controller (ACM8):
Input
Voltage 24VDC from eFlow104NB.
Main Fuse 10A / 32V.
Outputs
Voltage 24VDC.
Eight (8) independently controlled fused outputs:
a) Fail-Safe and/or Fail-Secure power outputs.
Form “C” Relays rated 28VAC or VDC @ 2.5A.
b) Auxiliary power outputs (unswitched).
c) Any combination of the above.
Output Fuses 3.5A / 32VDC.
Indicators (LED)
Red LEDs Outputs are triggered (relays energized).
Green LED FACP disconnect is triggered.
MaxFit7F8AP:
Physical and Environmental
Dimensions (H x W x D)
20.5” x 16.5” x 6.25” (520.7 mm x 419.1 mm x 158.8 mm).
Weight (approx.)
Product 26.9 lb. (12.2 kg).
Shipping 32.9 lb. (14.9 kg).
Temperature
Operating 0ºC to 50ºC (32ºF to 122ºF).
Storage -20ºC to 70ºC (-4ºF to 158ºF).
Relative Humidity 85% +/-5%.
BTU/Hr (approx.): 145 BTU/Hr.
Specifications
MaxFit7F8AP
Access Power Controller
Lifetime Warranty / Made in the U.S.A.
Altronix Corporation | 140 58th St | Brooklyn, NY 11220 USA
phone: +1 718.567.8181 | fax: +1 718.567.9056 | email: info@altronix.com | www.altronix.com