Spec Sheet
Power Supply (eFlow104NB):
Input
Voltage 120VAC, 60Hz, 4.5A max.
Input Fuse 6.3A/250V.
Outputs
Voltage 24VDC @ 10A.
Auxiliary 1A (unswitched).
Protection Overvoltage protection.
Filtered and regulated.
Battery Backup
Type Sealed lead acid or gel type.
Fuse Rating 10A/32VDC.
Failover Upon AC loss, instantaneous.
Fire Alarm Disconnect
Supervised Latching or non-latching.
EOL 10K Resistor.
Supervision
AC Failure Form “C” contacts.
Battery Form “C” contacts.
Low DC Power Shutdown
Shuts down DC output terminals if battery voltage drops below
70-75% for 24V units (depending on the power supply).
Prevents deep battery discharge.
Indicators (LED)
AC Input 120VAC is present.
DC Output Powered.
Battery Discharged or not connected.
Power Distribution Module (PD16W):
Input
Voltage 24VDC from eFlow104NB.
Outputs
Voltage 24VDC.
Sixteen (16) fuse protected outputs.
3.5A per output max.
Output Fuses 3.5A/250V.
Indicators (LED)
Green LED DC Output.
Voltage Regulator (VR6):
Input/Output
Voltage Range 24VDC @ 10A = Output: 12VDC @ 6A.
Output
12VDC regulated output.
Output rating 6A max.
Surge suppression.
Indicators (LED)
Input Indicates input voltage is present.
Output Indicates normal operating condition.
Dual Input Access Power Controllers (Two (2) ACMS8):
Input
Two (2) independent low voltage inputs.
Input Fuse 15A/32V.
Trigger Inputs:
Eight (8) individually controlled trigger inputs:
a) Normally open (NO) inputs.
b) Normally closed (NC) inputs.
c) Open collector sink inputs.
d) Wet Input (5VDC - 24VDC) with 10K resistor.
e) Any combination of the above.
Outputs
Fuse protected outputs rated @ 2.5A per output,
non power-limited. Total output 20A max.
Eight (8) selectable 12VDC - 24VDC independently controlled
outputs or eight (8) indepently controlled Form “C” relay outputs:
a) Fail-Safe and/or Fail-Secure power outputs.
b) Form “C” Relays. 28VAC or VDC @ 2.5A Rated.
c) Auxiliary power outputs (unswitched).
d) Any combination of the above.
Any of the eight (8) fuse protected power outputs are selectable
to follow power Input 1 or Input 2.
Individual outputs may be set to OFF position for servicing.
Output Fuses: 3A/32V each.
Total output current is determined by the power supply,
not to exceed a maximum of 10A for each input.
Fire Alarm Disconnect
Supervised Latching or non-latching, individually
selectable for any or all of the eight (8) outputs.
EOL 10K Resistor.
Indicators (LED)
Red LEDs Outputs are triggered (relays energized).
Blue LED FACP disconnect is triggered.
Individual voltage LEDs
Green: 12VDC
Red: 24VDC.
MaxFit7F16APS:
Physical and Environmental
Dimensions (H x W x D)
20.5” x 16.5” x 6.25” (520.7 mm x 419.1 mm x 158.8 mm).
Weight (approx.)
Product 28.1 lb. (12.75 kg).
Shipping 34.1 lb. (15.5 kg).
Temperature
Operating 0ºC to 50ºC (32ºF to 122ºF).
Storage -20ºC to 70ºC (-4ºF to 158ºF).
Relative Humidity 85% +/-5%.
BTU/Hr (approx.): 145 BTU/Hr.
Specifications
MaxFit7F16APS
Access Power Controller
Lifetime Warranty / Made in the U.S.A.
Altronix Corporation | 140 58th St | Brooklyn, NY 11220 USA
phone: +1 718.567.8181 | fax: +1 718.567.9056 | email: info@altronix.com | www.altronix.com