Installation Instructions Owner's manual

LED Diagnostics:
Red (DC) Green (AC) Power Supply Status
O
N ON Normal operating condition.
ON OFF Loss of AC, Stand-by battery supplying power.
OFF ON No DC output. Short circuit or thermal overload condition or defective unit.
OFF OFF No DC output. Loss of AC. Discharged or no battery present.
Terminal Identification:
Terminal Function/Description
Legend
AC/ AC Low voltage AC input (see voltage output/transformer selection table).
For 12VDC output use 16VAC with 56VA power rating or higher.
For 24VDC output use 28VAC with 85VA power rating or higher.
--- DC + 12VDC-24VDC @ 2.5 amp continuous output.
+ BAT --- Stand-by battery connections. Maximum charge rate 500mA.
AC FAIL Used to report loss of AC (e.g. connect to audible device or alarm panel).
N
.C., C, N.O. Relay normally energized when AC power is present.
(LPS3R only) Contact rating 1 amp @ 120VAC / 28VDC.
Altronix is not responsib
le for an
y typo
graphical errors. Product specifications are subject to change without notice.
140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056
website: www.altronix.com, e-mail: info@altronix.com, Lifetime Warranty, Made in U.S.A.